2026-02-02 10:27:59,685 INFO Start Time: 2026-02-02 10:27:59.685162
2026-02-02 10:27:59,685 INFO [MOCK] Serial terminal initialized
2026-02-02 10:27:59,685 INFO [MOCK] Serial terminal connected
2026-02-02 10:27:59,686 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:27:59,686 INFO The Test Operator check if the failure BIT in B6_MsgRdrSettingsAndParametersTellback changes ...
2026-02-02 10:27:59,686 INFO [MOCK] Log started at level 3 in directory: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts
2026-02-02 10:27:59,687 INFO tgt_gen_alone(): 0
2026-02-02 10:27:59,688 INFO tgt_gen()
2026-02-02 10:27:59,698 WARNING [MOCK] getSingleMessageReceivedSz called but interface not started! Returning 0
2026-02-02 10:27:59,698 DEBUG [MOCK] Field num: 1
2026-02-02 10:27:59,698 DEBUG [MOCK] Field rng: 1180
2026-02-02 10:27:59,698 INFO TgtMsg: 0 0
2026-02-02 10:27:59,699 INFO Tgt: 1 @ 1180
2026-02-02 10:27:59,699 INFO Check that B9 b9_t_num is between 1 and 2
2026-02-02 10:27:59,699 INFO OK: read value = 1
2026-02-02 10:27:59,699 INFO Check that B9 b9_t1_rng is between 1179 and 1186
2026-02-02 10:27:59,699 INFO OK: read value = 1180
2026-02-02 10:27:59,699 INFO [MOCK] Log stopped
2026-02-02 10:27:59,700 INFO Repetition 1 of 3
2026-02-02 10:27:59,700 DEBUG [MOCK] Serial statistics reset
2026-02-02 10:27:59,700 INFO The test operator is required to switch off the target and wait 3 seconds.
2026-02-02 10:28:00,700 INFO Set MAIN_POWER to False
2026-02-02 10:28:00,701 INFO [MOCK] Power OFF
2026-02-02 10:28:00,701 INFO [MOCK] 1553 Interface stopped
2026-02-02 10:28:05,701 INFO Check that MAIN_POWER is equal to 0
2026-02-02 10:28:05,702 INFO OK: read value = False
2026-02-02 10:28:09,702 INFO The test operator is required to switch on the target.
2026-02-02 10:28:09,704 INFO Set MAIN_POWER to True
2026-02-02 10:28:09,705 INFO [MOCK] Power ON
2026-02-02 10:28:09,707 INFO
====================================================================================================
[CRITICAL DEBUG] _initialize_field_values() CALLED
====================================================================================================
2026-02-02 10:28:09,707 INFO run_count = 1
2026-02-02 10:28:09,708 INFO SIMULATION_SCENARIO = 'mixed'
2026-02-02 10:28:09,708 INFO current_scenario = 'mixed'
2026-02-02 10:28:09,709 INFO _scenario_list = ['normal', 'recycle_fail_3', 'normal']
2026-02-02 10:28:09,709 INFO [DEBUG] Entering MIXED MODE branch
2026-02-02 10:28:09,710 INFO [DEBUG] Mixed mode: scenario_index=0, selected scenario='normal'
2026-02-02 10:28:09,710 INFO [DEBUG] About to call _log_scenario_info('normal', 1, 3)
2026-02-02 10:28:09,711 INFO
2026-02-02 10:28:09,711 INFO ####################################################################################################
2026-02-02 10:28:09,711 INFO ####################################################################################################
2026-02-02 10:28:09,712 INFO ### RUN 1/3: NORMAL OPERATION
2026-02-02 10:28:09,712 INFO ####################################################################################################
2026-02-02 10:28:09,712 INFO
2026-02-02 10:28:09,712 INFO SCENARIO: normal
2026-02-02 10:28:09,712 INFO DESCRIPTION: All systems operational - no failures
2026-02-02 10:28:09,713 INFO
2026-02-02 10:28:09,713 INFO EXPECTED FAILURES:
2026-02-02 10:28:09,714 INFO (none)
2026-02-02 10:28:09,714 INFO
2026-02-02 10:28:09,714 INFO EXPECTED PASSES:
2026-02-02 10:28:09,715 INFO ✓ All B6 status fields (except pedestal)
2026-02-02 10:28:09,715 INFO ✓ All B8 diagnostic fields
2026-02-02 10:28:09,715 INFO ✓ Target generation
2026-02-02 10:28:09,715 INFO
2026-02-02 10:28:09,715 INFO NOTES: Pedestal always fails due to HW test setup limitation (unit not present)
2026-02-02 10:28:09,715 INFO
2026-02-02 10:28:09,715 INFO ####################################################################################################
2026-02-02 10:28:09,716 INFO ####################################################################################################
2026-02-02 10:28:09,716 INFO
2026-02-02 10:28:09,716 INFO [DEBUG] _log_scenario_info() completed
2026-02-02 10:28:09,716 INFO [MOCK APPLY] ✓ All systems nominal (no failures injected)
2026-02-02 10:28:09,716 INFO [MOCK] 1553 Interface started - simulating BIT execution (Run 1)
2026-02-02 10:28:14,717 INFO Check that MAIN_POWER is equal to 1
2026-02-02 10:28:14,717 INFO OK: read value = True
2026-02-02 10:28:14,818 INFO [MOCK] BIT report available after 5.1s
2026-02-02 10:28:14,840 INFO BIT report available after 0.0s
2026-02-02 10:28:14,841 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_array_status is equal to false
2026-02-02 10:28:14,841 INFO OK: read value = false
2026-02-02 10:28:14,842 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status is equal to false
2026-02-02 10:28:14,842 WARNING CHECK ERROR: read value = true
2026-02-02 10:28:14,843 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 10:28:14,843 WARNING Known failure (ignored): radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status
2026-02-02 10:28:14,844 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pressurization_status is equal to false
2026-02-02 10:28:14,845 INFO OK: read value = false
2026-02-02 10:28:14,846 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_over_temperature_alarm is equal to false
2026-02-02 10:28:14,847 INFO OK: read value = false
2026-02-02 10:28:14,847 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_status is equal to false
2026-02-02 10:28:14,847 INFO OK: read value = false
2026-02-02 10:28:14,848 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_receiver_status is equal to false
2026-02-02 10:28:14,848 INFO OK: read value = false
2026-02-02 10:28:14,848 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_rx_front_end_status is equal to false
2026-02-02 10:28:14,848 INFO OK: read value = false
2026-02-02 10:28:14,849 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_over_temperature_alarm is equal to false
2026-02-02 10:28:14,849 INFO OK: read value = false
2026-02-02 10:28:14,849 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_status is equal to false
2026-02-02 10:28:14,849 INFO OK: read value = false
2026-02-02 10:28:14,850 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_over_temperature_alarm is equal to false
2026-02-02 10:28:14,850 INFO OK: read value = false
2026-02-02 10:28:14,850 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_status is equal to false
2026-02-02 10:28:14,850 INFO OK: read value = false
2026-02-02 10:28:14,851 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_radar_fail_status is equal to false
2026-02-02 10:28:14,851 WARNING CHECK ERROR: read value = RDR_OK
2026-02-02 10:28:14,851 ERROR INTERFACE ERROR: Expected false, got RDR_OK
2026-02-02 10:28:14,851 WARNING Radar fail status: Known failure (caused only by pedestal)
2026-02-02 10:28:14,851 INFO [Run 1] B6 LRU Status: 12 total, 10 pass, 0 fail, 2 known
2026-02-02 10:28:14,851 INFO Known failures (HW setup): 2
2026-02-02 10:28:14,852 INFO
Forced B8 drill-down (FORCE_B8_DRILL_DOWN=True): Verifying all 173 B8 diagnostic fields...
2026-02-02 10:28:14,852 INFO [FORCE_B8_DRILL_DOWN] Performing B8 drill-down despite only known failures
2026-02-02 10:28:14,852 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_bcn_fail is equal to false
2026-02-02 10:28:14,852 INFO OK: read value = false
2026-02-02 10:28:14,852 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_gm_rbm_sea1_ta_wa_fail is equal to false
2026-02-02 10:28:14,853 INFO OK: read value = false
2026-02-02 10:28:14,853 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group1_fail is equal to false
2026-02-02 10:28:14,853 INFO OK: read value = false
2026-02-02 10:28:14,853 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group2_fail is equal to false
2026-02-02 10:28:14,854 INFO OK: read value = false
2026-02-02 10:28:14,854 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group3_fail is equal to false
2026-02-02 10:28:14,854 INFO OK: read value = false
2026-02-02 10:28:14,855 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group4_fail is equal to false
2026-02-02 10:28:14,855 INFO OK: read value = false
2026-02-02 10:28:14,855 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group5_fail is equal to false
2026-02-02 10:28:14,855 INFO OK: read value = false
2026-02-02 10:28:14,855 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_hr_modes_and_gm_dbs_fail is equal to false
2026-02-02 10:28:14,856 INFO OK: read value = false
2026-02-02 10:28:14,856 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_no_rdr_symbology is equal to false
2026-02-02 10:28:14,856 INFO OK: read value = false
2026-02-02 10:28:14,856 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_not_identified_rdr_fail is equal to false
2026-02-02 10:28:14,857 WARNING CHECK ERROR: read value = 0
2026-02-02 10:28:14,857 ERROR INTERFACE ERROR: Expected false, got 0
2026-02-02 10:28:14,857 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_selected_channel_fail is equal to false
2026-02-02 10:28:14,857 INFO OK: read value = false
2026-02-02 10:28:14,857 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_total_rdr_fail is equal to false
2026-02-02 10:28:14,858 INFO OK: read value = false
2026-02-02 10:28:14,858 WARNING B8_Degradation: 1/12 failures
2026-02-02 10:28:14,858 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru1_gimbal is equal to false
2026-02-02 10:28:14,859 INFO OK: read value = false
2026-02-02 10:28:14,859 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru2_waveguide is equal to false
2026-02-02 10:28:14,859 INFO OK: read value = false
2026-02-02 10:28:14,860 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru3_waveguide is equal to false
2026-02-02 10:28:14,860 INFO OK: read value = false
2026-02-02 10:28:14,860 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru4_delta_guard_lna_switch is equal to false
2026-02-02 10:28:14,861 INFO OK: read value = false
2026-02-02 10:28:14,861 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru5_waveguide_switch is equal to false
2026-02-02 10:28:14,861 INFO OK: read value = false
2026-02-02 10:28:14,862 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru10_main_computer is equal to false
2026-02-02 10:28:14,862 INFO OK: read value = false
2026-02-02 10:28:14,863 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru11_graphic_computer is equal to false
2026-02-02 10:28:14,863 INFO OK: read value = false
2026-02-02 10:28:14,863 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru12_power_supply is equal to false
2026-02-02 10:28:14,863 INFO OK: read value = false
2026-02-02 10:28:14,863 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru13_det_exp is equal to false
2026-02-02 10:28:14,864 INFO OK: read value = false
2026-02-02 10:28:14,864 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru14_rx_module is equal to false
2026-02-02 10:28:14,864 INFO OK: read value = false
2026-02-02 10:28:14,864 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru1_motherboard_chassis is equal to false
2026-02-02 10:28:14,864 INFO OK: read value = false
2026-02-02 10:28:14,864 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru2_mti_fft is equal to false
2026-02-02 10:28:14,864 INFO OK: read value = false
2026-02-02 10:28:14,865 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru3_dsp0 is equal to false
2026-02-02 10:28:14,865 INFO OK: read value = false
2026-02-02 10:28:14,865 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru4_dsp1 is equal to false
2026-02-02 10:28:14,865 INFO OK: read value = false
2026-02-02 10:28:14,865 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru5_cfar_px_ctrl is equal to false
2026-02-02 10:28:14,865 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru6_timer is equal to false
2026-02-02 10:28:14,866 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru7_post_processor is equal to false
2026-02-02 10:28:14,866 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru8_agc is equal to false
2026-02-02 10:28:14,866 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru9_esa_if is equal to false
2026-02-02 10:28:14,866 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru1_chassis is equal to false
2026-02-02 10:28:14,866 INFO OK: read value = false
2026-02-02 10:28:14,866 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru2_uhf_assy is equal to false
2026-02-02 10:28:14,867 INFO OK: read value = false
2026-02-02 10:28:14,867 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru3_synthesizer is equal to false
2026-02-02 10:28:14,867 INFO OK: read value = false
2026-02-02 10:28:14,867 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru4_delta_guard_down_converter is equal to false
2026-02-02 10:28:14,867 INFO OK: read value = false
2026-02-02 10:28:14,868 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru5_sum_down_converter is equal to false
2026-02-02 10:28:14,868 INFO OK: read value = false
2026-02-02 10:28:14,868 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru6_lo_distributor is equal to false
2026-02-02 10:28:14,868 INFO OK: read value = false
2026-02-02 10:28:14,868 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru7_up_converter is equal to false
2026-02-02 10:28:14,869 INFO OK: read value = false
2026-02-02 10:28:14,869 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru1_chassis is equal to false
2026-02-02 10:28:14,869 INFO OK: read value = false
2026-02-02 10:28:14,869 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru2_delta_guard_lna is equal to false
2026-02-02 10:28:14,869 INFO OK: read value = false
2026-02-02 10:28:14,869 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru3_sum_act_prot_lna is equal to false
2026-02-02 10:28:14,869 INFO OK: read value = false
2026-02-02 10:28:14,869 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru4_4port_circulator is equal to false
2026-02-02 10:28:14,870 INFO OK: read value = false
2026-02-02 10:28:14,870 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_delta_guard is equal to false
2026-02-02 10:28:14,870 INFO OK: read value = false
2026-02-02 10:28:14,870 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_sum is equal to false
2026-02-02 10:28:14,870 INFO OK: read value = false
2026-02-02 10:28:14,870 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru1_chassis is equal to false
2026-02-02 10:28:14,870 INFO OK: read value = false
2026-02-02 10:28:14,870 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru2_power_supply is equal to false
2026-02-02 10:28:14,870 INFO OK: read value = false
2026-02-02 10:28:14,871 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru3_digital_controller is equal to false
2026-02-02 10:28:14,871 INFO OK: read value = false
2026-02-02 10:28:14,871 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru1_chassis is equal to false
2026-02-02 10:28:14,871 INFO OK: read value = false
2026-02-02 10:28:14,871 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru2_rex_f_tx is equal to false
2026-02-02 10:28:14,871 INFO OK: read value = false
2026-02-02 10:28:14,871 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru3_power_supply is equal to false
2026-02-02 10:28:14,871 INFO OK: read value = false
2026-02-02 10:28:14,872 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru4_valve_el_twt_tx is equal to false
2026-02-02 10:28:14,872 INFO OK: read value = false
2026-02-02 10:28:14,872 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru5_rf_driver is equal to false
2026-02-02 10:28:14,872 INFO OK: read value = false
2026-02-02 10:28:14,872 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru6_controller_tx is equal to false
2026-02-02 10:28:14,872 INFO OK: read value = false
2026-02-02 10:28:14,872 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru7_hv_power_supply is equal to false
2026-02-02 10:28:14,873 INFO OK: read value = false
2026-02-02 10:28:14,873 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru8_eht_power_supply is equal to false
2026-02-02 10:28:14,873 INFO OK: read value = false
2026-02-02 10:28:14,874 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc10_pulse_compressor_interface is equal to false
2026-02-02 10:28:14,874 INFO OK: read value = false
2026-02-02 10:28:14,874 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc11_dp_interface is equal to false
2026-02-02 10:28:14,874 INFO OK: read value = false
2026-02-02 10:28:14,875 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc13_taxi_running is equal to false
2026-02-02 10:28:14,875 INFO OK: read value = false
2026-02-02 10:28:14,875 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc14_external_xyp_ram is equal to false
2026-02-02 10:28:14,876 INFO OK: read value = false
2026-02-02 10:28:14,876 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc15_servoloop_interface is equal to false
2026-02-02 10:28:14,876 INFO OK: read value = false
2026-02-02 10:28:14,877 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc1_internal_xyp_ram is equal to false
2026-02-02 10:28:14,878 INFO OK: read value = false
2026-02-02 10:28:14,878 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc2_external_xyp_ram is equal to false
2026-02-02 10:28:14,878 INFO OK: read value = false
2026-02-02 10:28:14,878 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc5_dual_port_ram is equal to false
2026-02-02 10:28:14,879 INFO OK: read value = false
2026-02-02 10:28:14,879 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc6_agc_machine is equal to false
2026-02-02 10:28:14,879 INFO OK: read value = false
2026-02-02 10:28:14,879 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc7_sat_machine is equal to false
2026-02-02 10:28:14,880 INFO OK: read value = false
2026-02-02 10:28:14,880 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc9_c_ram_xy_checksum is equal to false
2026-02-02 10:28:14,880 INFO OK: read value = false
2026-02-02 10:28:14,880 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp10_video_memory is equal to false
2026-02-02 10:28:14,880 INFO OK: read value = false
2026-02-02 10:28:14,880 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp11_video_unit is equal to false
2026-02-02 10:28:14,881 INFO OK: read value = false
2026-02-02 10:28:14,881 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp12_transputer_unit is equal to false
2026-02-02 10:28:14,881 INFO OK: read value = false
2026-02-02 10:28:14,881 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp13_scan_converter_polar_memory is equal to false
2026-02-02 10:28:14,881 INFO OK: read value = false
2026-02-02 10:28:14,882 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp14_scan_converter_format_converter is equal to false
2026-02-02 10:28:14,883 INFO OK: read value = false
2026-02-02 10:28:14,883 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp1_486_cpu_tests is equal to false
2026-02-02 10:28:14,883 INFO OK: read value = false
2026-02-02 10:28:14,884 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp2_486_interfaces_with_r3000_gc is equal to false
2026-02-02 10:28:14,884 INFO OK: read value = false
2026-02-02 10:28:14,884 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp3_486_interface_with_slc is equal to false
2026-02-02 10:28:14,884 INFO OK: read value = false
2026-02-02 10:28:14,884 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp4_slc_communications is equal to false
2026-02-02 10:28:14,885 INFO OK: read value = false
2026-02-02 10:28:14,885 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp5_r3000_cpu_tests is equal to false
2026-02-02 10:28:14,885 INFO OK: read value = false
2026-02-02 10:28:14,885 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp6_r3000_interfaces is equal to false
2026-02-02 10:28:14,885 INFO OK: read value = false
2026-02-02 10:28:14,885 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp7_1553_and_discretes is equal to false
2026-02-02 10:28:14,886 INFO OK: read value = false
2026-02-02 10:28:14,886 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp8_graphic_cpu is equal to false
2026-02-02 10:28:14,886 INFO OK: read value = false
2026-02-02 10:28:14,886 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp9_graphic_processors is equal to false
2026-02-02 10:28:14,886 INFO OK: read value = false
2026-02-02 10:28:14,886 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_array_status is equal to false
2026-02-02 10:28:14,887 INFO OK: read value = false
2026-02-02 10:28:14,887 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_delta_channel_fail is equal to false
2026-02-02 10:28:14,887 INFO OK: read value = false
2026-02-02 10:28:14,887 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_injection_fail is equal to false
2026-02-02 10:28:14,887 INFO OK: read value = false
2026-02-02 10:28:14,888 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_noise_fail is equal to false
2026-02-02 10:28:14,888 INFO OK: read value = false
2026-02-02 10:28:14,888 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_pedestal_status is equal to false
2026-02-02 10:28:14,888 INFO OK: read value = false
2026-02-02 10:28:14,888 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_processor_status is equal to false
2026-02-02 10:28:14,889 INFO OK: read value = false
2026-02-02 10:28:14,889 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_receiver_status is equal to false
2026-02-02 10:28:14,889 INFO OK: read value = false
2026-02-02 10:28:14,890 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_rx_frontend_status is equal to false
2026-02-02 10:28:14,890 INFO OK: read value = false
2026-02-02 10:28:14,891 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_servoloop_status is equal to false
2026-02-02 10:28:14,891 INFO OK: read value = false
2026-02-02 10:28:14,891 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is1_upconverter_chain_levels is equal to false
2026-02-02 10:28:14,891 INFO OK: read value = false
2026-02-02 10:28:14,891 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is2_downconverter_chain_levels is equal to false
2026-02-02 10:28:14,892 INFO OK: read value = false
2026-02-02 10:28:14,892 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is3_antenna_status_inconsistent is equal to false
2026-02-02 10:28:14,892 INFO OK: read value = false
2026-02-02 10:28:14,892 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is4_tx_status_inconsistent is equal to false
2026-02-02 10:28:14,892 INFO OK: read value = false
2026-02-02 10:28:14,893 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is5_tx_power_level is equal to false
2026-02-02 10:28:14,893 INFO OK: read value = false
2026-02-02 10:28:14,893 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_transmitter_status is equal to false
2026-02-02 10:28:14,893 INFO OK: read value = false
2026-02-02 10:28:14,893 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp1_master_dsp is equal to false
2026-02-02 10:28:14,893 INFO OK: read value = false
2026-02-02 10:28:14,893 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp2_interface_card is equal to false
2026-02-02 10:28:14,894 INFO OK: read value = false
2026-02-02 10:28:14,894 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp3_cpu_cards is equal to false
2026-02-02 10:28:14,894 INFO OK: read value = false
2026-02-02 10:28:14,894 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp4_dma_bus is equal to false
2026-02-02 10:28:14,894 INFO OK: read value = false
2026-02-02 10:28:14,894 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp5_sp_interface is equal to false
2026-02-02 10:28:14,894 INFO OK: read value = false
2026-02-02 10:28:14,895 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp6_dp_interface is equal to false
2026-02-02 10:28:14,895 INFO OK: read value = false
2026-02-02 10:28:14,895 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp7_scan_converter_interface is equal to false
2026-02-02 10:28:14,895 INFO OK: read value = false
2026-02-02 10:28:14,895 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp8_agc_interface is equal to false
2026-02-02 10:28:14,895 INFO OK: read value = false
2026-02-02 10:28:14,895 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps1_power_supply is equal to false
2026-02-02 10:28:14,895 INFO OK: read value = false
2026-02-02 10:28:14,896 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps2_over_temperature is equal to false
2026-02-02 10:28:14,896 INFO OK: read value = false
2026-02-02 10:28:14,896 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe1_lna is equal to false
2026-02-02 10:28:14,896 INFO OK: read value = false
2026-02-02 10:28:14,896 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe2_agc_attenuators is equal to false
2026-02-02 10:28:14,896 INFO OK: read value = false
2026-02-02 10:28:14,896 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx1_synthesizer_commands is equal to false
2026-02-02 10:28:14,897 INFO OK: read value = false
2026-02-02 10:28:14,897 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx2_synthesizer_internal_tests is equal to false
2026-02-02 10:28:14,897 INFO OK: read value = false
2026-02-02 10:28:14,897 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx3_uhf_oscillator_level is equal to false
2026-02-02 10:28:14,897 INFO OK: read value = false
2026-02-02 10:28:14,897 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx4_downconverter_lo_level is equal to false
2026-02-02 10:28:14,897 INFO OK: read value = false
2026-02-02 10:28:14,897 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx5_upconverter_lo_level is equal to false
2026-02-02 10:28:14,897 INFO OK: read value = false
2026-02-02 10:28:14,898 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm16_calibration_sum_channel_fail is equal to false
2026-02-02 10:28:14,898 INFO OK: read value = false
2026-02-02 10:28:14,898 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm1_master_clock_level is equal to false
2026-02-02 10:28:14,898 INFO OK: read value = false
2026-02-02 10:28:14,898 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm2_expander_level is equal to false
2026-02-02 10:28:14,898 INFO OK: read value = false
2026-02-02 10:28:14,898 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm3_sum_channel_down_converter is equal to false
2026-02-02 10:28:14,898 INFO OK: read value = false
2026-02-02 10:28:14,898 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm4_dg_channel_down_converter is equal to false
2026-02-02 10:28:14,899 INFO OK: read value = false
2026-02-02 10:28:14,899 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm5_noise_attenuators is equal to false
2026-02-02 10:28:14,899 INFO OK: read value = false
2026-02-02 10:28:14,899 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl10_agc_control is equal to false
2026-02-02 10:28:14,899 INFO OK: read value = false
2026-02-02 10:28:14,899 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl11_ad is equal to false
2026-02-02 10:28:14,900 INFO OK: read value = false
2026-02-02 10:28:14,900 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl12_das is equal to false
2026-02-02 10:28:14,900 INFO OK: read value = false
2026-02-02 10:28:14,900 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl13_serial_communications is equal to false
2026-02-02 10:28:14,900 INFO OK: read value = false
2026-02-02 10:28:14,900 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl14_taxi_interface is equal to false
2026-02-02 10:28:14,900 INFO OK: read value = false
2026-02-02 10:28:14,900 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl15_pedestal_centre_scan_location is equal to false
2026-02-02 10:28:14,900 INFO OK: read value = false
2026-02-02 10:28:14,900 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl1_low_voltage_power_supply is equal to false
2026-02-02 10:28:14,901 INFO OK: read value = false
2026-02-02 10:28:14,901 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl2_high_voltage_power_supply is equal to false
2026-02-02 10:28:14,901 INFO OK: read value = false
2026-02-02 10:28:14,901 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl3_motor_drivers is equal to false
2026-02-02 10:28:14,901 INFO OK: read value = false
2026-02-02 10:28:14,901 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl4_resolvers_power_supply is equal to false
2026-02-02 10:28:14,901 INFO OK: read value = false
2026-02-02 10:28:14,901 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl5_waveguide_switch is equal to false
2026-02-02 10:28:14,902 INFO OK: read value = false
2026-02-02 10:28:14,902 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl6_over_temperature is equal to false
2026-02-02 10:28:14,902 INFO OK: read value = false
2026-02-02 10:28:14,902 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl7_resolver_to_digital_conv is equal to false
2026-02-02 10:28:14,902 INFO OK: read value = false
2026-02-02 10:28:14,902 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl8_position_loop_error is equal to false
2026-02-02 10:28:14,902 INFO OK: read value = false
2026-02-02 10:28:14,903 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl9_microprocessor is equal to false
2026-02-02 10:28:14,903 INFO OK: read value = false
2026-02-02 10:28:14,903 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp10_board_overall is equal to false
2026-02-02 10:28:14,903 INFO OK: read value = false
2026-02-02 10:28:14,904 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp11_attenuatori_antenna is equal to false
2026-02-02 10:28:14,904 INFO OK: read value = false
2026-02-02 10:28:14,905 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp14_external_sp_if is equal to false
2026-02-02 10:28:14,905 INFO OK: read value = false
2026-02-02 10:28:14,906 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp16_bcn is equal to false
2026-02-02 10:28:14,906 INFO OK: read value = false
2026-02-02 10:28:14,906 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp1_timer1_up is equal to false
2026-02-02 10:28:14,907 INFO OK: read value = false
2026-02-02 10:28:14,907 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp2_timer_dma_pxc_if is equal to false
2026-02-02 10:28:14,907 INFO OK: read value = false
2026-02-02 10:28:14,907 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp3_timer_internal is equal to false
2026-02-02 10:28:14,908 INFO OK: read value = false
2026-02-02 10:28:14,908 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp4_px_ctrl_comm is equal to false
2026-02-02 10:28:14,909 INFO OK: read value = false
2026-02-02 10:28:14,910 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp5_video1_without_ad is equal to false
2026-02-02 10:28:14,910 INFO OK: read value = false
2026-02-02 10:28:14,910 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp6_video1_with_ad is equal to false
2026-02-02 10:28:14,911 INFO OK: read value = false
2026-02-02 10:28:14,911 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp7_video2_ad_sync is equal to false
2026-02-02 10:28:14,911 INFO OK: read value = false
2026-02-02 10:28:14,911 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp8_video2_timer_sync is equal to false
2026-02-02 10:28:14,911 INFO OK: read value = false
2026-02-02 10:28:14,912 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9_ad_da is equal to false
2026-02-02 10:28:14,912 INFO OK: read value = false
2026-02-02 10:28:14,912 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9b_wideband_expander is equal to false
2026-02-02 10:28:14,912 INFO OK: read value = false
2026-02-02 10:28:14,912 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx10_hv_ps_over_temperature_warning is equal to false
2026-02-02 10:28:14,913 INFO OK: read value = false
2026-02-02 10:28:14,913 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx11_twt_helix_over_current is equal to false
2026-02-02 10:28:14,913 INFO OK: read value = false
2026-02-02 10:28:14,913 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx12_cathode_to_helix_arc is equal to false
2026-02-02 10:28:14,914 INFO OK: read value = false
2026-02-02 10:28:14,914 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx13_twt_over_temperature_hazard is equal to false
2026-02-02 10:28:14,915 INFO OK: read value = false
2026-02-02 10:28:14,915 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx14_twt_over_temperature_warning is equal to false
2026-02-02 10:28:14,915 INFO OK: read value = false
2026-02-02 10:28:14,915 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx15_cathode_under_voltage is equal to false
2026-02-02 10:28:14,915 INFO OK: read value = false
2026-02-02 10:28:14,915 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx16_cathode_over_voltage is equal to false
2026-02-02 10:28:14,916 INFO OK: read value = false
2026-02-02 10:28:14,916 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx1_microprocessors is equal to false
2026-02-02 10:28:14,916 INFO OK: read value = false
2026-02-02 10:28:14,917 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx2_tx_rf_input is equal to false
2026-02-02 10:28:14,917 INFO OK: read value = false
2026-02-02 10:28:14,917 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx3_twt_rf_input is equal to false
2026-02-02 10:28:14,918 INFO OK: read value = false
2026-02-02 10:28:14,918 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx4_twt_rf_output is equal to false
2026-02-02 10:28:14,918 INFO OK: read value = false
2026-02-02 10:28:14,919 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx5_tx_rf_output_level is equal to false
2026-02-02 10:28:14,919 INFO OK: read value = false
2026-02-02 10:28:14,919 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx6_vswr is equal to false
2026-02-02 10:28:14,919 INFO OK: read value = false
2026-02-02 10:28:14,920 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx7_three_phase_input_power is equal to false
2026-02-02 10:28:14,920 INFO OK: read value = false
2026-02-02 10:28:14,920 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx8_low_voltage_power_supplies is equal to false
2026-02-02 10:28:14,920 INFO OK: read value = false
2026-02-02 10:28:14,921 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx9_hv_ps_over_temperature_hazard is equal to false
2026-02-02 10:28:14,921 INFO OK: read value = false
2026-02-02 10:28:14,921 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx17_collector_under_voltage is equal to false
2026-02-02 10:28:14,921 INFO OK: read value = false
2026-02-02 10:28:14,921 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx18_collector_over_voltage is equal to false
2026-02-02 10:28:14,922 INFO OK: read value = false
2026-02-02 10:28:14,922 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx19_rectified_voltage is equal to false
2026-02-02 10:28:14,922 INFO OK: read value = false
2026-02-02 10:28:14,922 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx20_cathode_inv_current_fail is equal to false
2026-02-02 10:28:14,922 INFO OK: read value = false
2026-02-02 10:28:14,922 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx21_collector_inv_current_fail is equal to false
2026-02-02 10:28:14,923 INFO OK: read value = false
2026-02-02 10:28:14,923 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx22_waveguide_pressurization is equal to false
2026-02-02 10:28:14,923 INFO OK: read value = false
2026-02-02 10:28:14,923 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx23_grid_window_over_duty_alt is equal to false
2026-02-02 10:28:14,924 INFO OK: read value = false
2026-02-02 10:28:14,924 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx24_floating_deck_fail is equal to false
2026-02-02 10:28:14,924 INFO OK: read value = false
2026-02-02 10:28:14,924 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx25_floating_deck_ps_fail is equal to false
2026-02-02 10:28:14,924 INFO OK: read value = false
2026-02-02 10:28:14,924 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx26_grid_window_over_duty is equal to false
2026-02-02 10:28:14,924 INFO OK: read value = false
2026-02-02 10:28:14,925 INFO [Run 1] B8 Diagnostics: 173 checked, 172 pass, 1 fail
2026-02-02 10:28:14,925 WARNING B8_Degradation: 1 failures - fail
2026-02-02 10:28:14,925 INFO 0.0s remaining ...
2026-02-02 10:28:14,925 INFO [Run 1] Serial: 0 total, 0 errors, 0 fatal, 0 recycles
2026-02-02 10:28:14,925 WARNING Session: GRIFO_M_PBIT : Repetition 1 of 3
Total Step 191: Success 188 (98.43%), Failed 3 (1.57%),
2026-02-02 10:28:14,925 INFO Repetition 2 of 3
2026-02-02 10:28:14,926 DEBUG [MOCK] Serial statistics reset
2026-02-02 10:28:14,926 INFO The test operator is required to switch off the target and wait 3 seconds.
2026-02-02 10:28:15,926 INFO Set MAIN_POWER to False
2026-02-02 10:28:15,930 INFO [MOCK] Power OFF
2026-02-02 10:28:15,930 INFO [MOCK] 1553 Interface stopped
2026-02-02 10:28:20,933 INFO Check that MAIN_POWER is equal to 0
2026-02-02 10:28:20,934 INFO OK: read value = False
2026-02-02 10:28:24,936 INFO The test operator is required to switch on the target.
2026-02-02 10:28:24,937 INFO Set MAIN_POWER to True
2026-02-02 10:28:24,937 INFO [MOCK] Power ON
2026-02-02 10:28:24,938 INFO
====================================================================================================
[CRITICAL DEBUG] _initialize_field_values() CALLED
====================================================================================================
2026-02-02 10:28:24,938 INFO run_count = 2
2026-02-02 10:28:24,938 INFO SIMULATION_SCENARIO = 'mixed'
2026-02-02 10:28:24,939 INFO current_scenario = 'mixed'
2026-02-02 10:28:24,939 INFO _scenario_list = ['normal', 'recycle_fail_3', 'normal']
2026-02-02 10:28:24,939 INFO [DEBUG] Entering MIXED MODE branch
2026-02-02 10:28:24,939 INFO [DEBUG] Mixed mode: scenario_index=1, selected scenario='recycle_fail_3'
2026-02-02 10:28:24,939 INFO [DEBUG] About to call _log_scenario_info('recycle_fail_3', 2, 3)
2026-02-02 10:28:24,939 INFO
2026-02-02 10:28:24,939 INFO ####################################################################################################
2026-02-02 10:28:24,939 INFO ####################################################################################################
2026-02-02 10:28:24,940 INFO ### RUN 2/3: RECYCLE NO RECOVERY (3+ CYCLES)
2026-02-02 10:28:24,940 INFO ####################################################################################################
2026-02-02 10:28:24,940 INFO
2026-02-02 10:28:24,940 INFO SCENARIO: recycle_fail_3
2026-02-02 10:28:24,940 INFO DESCRIPTION: Processor fails and NEVER recovers despite 3 RECYCLE events
2026-02-02 10:28:24,940 INFO
2026-02-02 10:28:24,940 INFO EXPECTED FAILURES:
2026-02-02 10:28:24,940 INFO ✗ Persistent: processor_status = FAIL
2026-02-02 10:28:24,940 INFO ✗ Serial: 3x RECYCLE events detected
2026-02-02 10:28:24,941 INFO ✗ No recovery achieved
2026-02-02 10:28:24,941 INFO
2026-02-02 10:28:24,941 INFO EXPECTED PASSES:
2026-02-02 10:28:24,942 INFO ✓ None - system remains in failed state
2026-02-02 10:28:24,943 INFO
2026-02-02 10:28:24,943 INFO NOTES: Simulates hard failure requiring power cycle. Test should fail and report persistent failure
2026-02-02 10:28:24,943 INFO
2026-02-02 10:28:24,943 INFO ####################################################################################################
2026-02-02 10:28:24,943 INFO ####################################################################################################
2026-02-02 10:28:24,943 INFO
2026-02-02 10:28:24,944 INFO [DEBUG] _log_scenario_info() completed
2026-02-02 10:28:24,944 INFO [MOCK APPLY] ⚠ RECYCLE scenario enabled: NO recovery (persistent failure)
2026-02-02 10:28:24,944 INFO [MOCK RECYCLE] Initial processor failure detected
2026-02-02 10:28:25,445 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:25,445 INFO [MOCK RECYCLE] RECYCLE 1/3 - NO RECOVERY
2026-02-02 10:28:25,946 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:25,946 INFO [MOCK RECYCLE] RECYCLE 2/3 - NO RECOVERY
2026-02-02 10:28:26,448 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:26,448 INFO [MOCK RECYCLE] RECYCLE 3/3 - NO RECOVERY
2026-02-02 10:28:26,449 WARNING [MOCK RECYCLE] System did NOT recover after 3 RECYCLEs - requires power cycle
2026-02-02 10:28:26,449 INFO [MOCK] 1553 Interface started - simulating BIT execution (Run 2)
2026-02-02 10:28:31,450 INFO Check that MAIN_POWER is equal to 1
2026-02-02 10:28:31,450 INFO OK: read value = True
2026-02-02 10:28:31,551 INFO [MOCK] BIT report available after 6.6s
2026-02-02 10:28:31,572 INFO BIT report available after 0.0s
2026-02-02 10:28:31,572 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_array_status is equal to false
2026-02-02 10:28:31,573 INFO OK: read value = false
2026-02-02 10:28:31,573 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status is equal to false
2026-02-02 10:28:31,573 WARNING CHECK ERROR: read value = true
2026-02-02 10:28:31,573 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 10:28:31,574 WARNING Known failure (ignored): radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status
2026-02-02 10:28:31,574 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pressurization_status is equal to false
2026-02-02 10:28:31,574 INFO OK: read value = false
2026-02-02 10:28:31,574 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_over_temperature_alarm is equal to false
2026-02-02 10:28:31,574 INFO OK: read value = false
2026-02-02 10:28:31,575 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_status is equal to false
2026-02-02 10:28:31,575 WARNING CHECK ERROR: read value = true
2026-02-02 10:28:31,575 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 10:28:31,575 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_receiver_status is equal to false
2026-02-02 10:28:31,576 INFO OK: read value = false
2026-02-02 10:28:31,576 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_rx_front_end_status is equal to false
2026-02-02 10:28:31,576 INFO OK: read value = false
2026-02-02 10:28:31,576 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_over_temperature_alarm is equal to false
2026-02-02 10:28:31,576 INFO OK: read value = false
2026-02-02 10:28:31,576 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_status is equal to false
2026-02-02 10:28:31,577 INFO OK: read value = false
2026-02-02 10:28:31,577 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_over_temperature_alarm is equal to false
2026-02-02 10:28:31,577 INFO OK: read value = false
2026-02-02 10:28:31,577 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_status is equal to false
2026-02-02 10:28:31,578 INFO OK: read value = false
2026-02-02 10:28:31,578 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_radar_fail_status is equal to false
2026-02-02 10:28:31,578 WARNING CHECK ERROR: read value = RDR_FAIL
2026-02-02 10:28:31,578 ERROR INTERFACE ERROR: Expected false, got RDR_FAIL
2026-02-02 10:28:31,578 WARNING Radar fail status: REAL failure (caused by: status, status)
2026-02-02 10:28:31,578 INFO [Run 2] B6 LRU Status: 12 total, 9 pass, 2 fail, 1 known
2026-02-02 10:28:31,578 INFO Known failures (HW setup): 1
2026-02-02 10:28:31,578 WARNING Real failures: status, status
2026-02-02 10:28:31,579 INFO
Drill-down: Verifying all 173 B8 diagnostic fields...
2026-02-02 10:28:31,579 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_bcn_fail is equal to false
2026-02-02 10:28:31,579 INFO OK: read value = false
2026-02-02 10:28:31,579 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_gm_rbm_sea1_ta_wa_fail is equal to false
2026-02-02 10:28:31,579 INFO OK: read value = false
2026-02-02 10:28:31,579 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group1_fail is equal to false
2026-02-02 10:28:31,580 INFO OK: read value = false
2026-02-02 10:28:31,580 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group2_fail is equal to false
2026-02-02 10:28:31,580 INFO OK: read value = false
2026-02-02 10:28:31,580 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group3_fail is equal to false
2026-02-02 10:28:31,580 INFO OK: read value = false
2026-02-02 10:28:31,580 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group4_fail is equal to false
2026-02-02 10:28:31,580 INFO OK: read value = false
2026-02-02 10:28:31,581 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group5_fail is equal to false
2026-02-02 10:28:31,581 INFO OK: read value = false
2026-02-02 10:28:31,581 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_hr_modes_and_gm_dbs_fail is equal to false
2026-02-02 10:28:31,581 INFO OK: read value = false
2026-02-02 10:28:31,581 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_no_rdr_symbology is equal to false
2026-02-02 10:28:31,581 INFO OK: read value = false
2026-02-02 10:28:31,581 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_not_identified_rdr_fail is equal to false
2026-02-02 10:28:31,581 WARNING CHECK ERROR: read value = 0
2026-02-02 10:28:31,581 ERROR INTERFACE ERROR: Expected false, got 0
2026-02-02 10:28:31,582 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_selected_channel_fail is equal to false
2026-02-02 10:28:31,582 INFO OK: read value = false
2026-02-02 10:28:31,582 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_total_rdr_fail is equal to false
2026-02-02 10:28:31,582 INFO OK: read value = false
2026-02-02 10:28:31,582 WARNING B8_Degradation: 1/12 failures
2026-02-02 10:28:31,583 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru1_gimbal is equal to false
2026-02-02 10:28:31,583 INFO OK: read value = false
2026-02-02 10:28:31,583 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru2_waveguide is equal to false
2026-02-02 10:28:31,583 INFO OK: read value = false
2026-02-02 10:28:31,583 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru3_waveguide is equal to false
2026-02-02 10:28:31,584 INFO OK: read value = false
2026-02-02 10:28:31,584 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru4_delta_guard_lna_switch is equal to false
2026-02-02 10:28:31,584 INFO OK: read value = false
2026-02-02 10:28:31,584 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru5_waveguide_switch is equal to false
2026-02-02 10:28:31,584 INFO OK: read value = false
2026-02-02 10:28:31,584 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru10_main_computer is equal to false
2026-02-02 10:28:31,585 INFO OK: read value = false
2026-02-02 10:28:31,585 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru11_graphic_computer is equal to false
2026-02-02 10:28:31,585 INFO OK: read value = false
2026-02-02 10:28:31,585 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru12_power_supply is equal to false
2026-02-02 10:28:31,585 INFO OK: read value = false
2026-02-02 10:28:31,585 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru13_det_exp is equal to false
2026-02-02 10:28:31,586 INFO OK: read value = false
2026-02-02 10:28:31,586 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru14_rx_module is equal to false
2026-02-02 10:28:31,586 INFO OK: read value = false
2026-02-02 10:28:31,586 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru1_motherboard_chassis is equal to false
2026-02-02 10:28:31,586 INFO OK: read value = false
2026-02-02 10:28:31,586 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru2_mti_fft is equal to false
2026-02-02 10:28:31,586 INFO OK: read value = false
2026-02-02 10:28:31,587 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru3_dsp0 is equal to false
2026-02-02 10:28:31,587 INFO OK: read value = false
2026-02-02 10:28:31,587 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru4_dsp1 is equal to false
2026-02-02 10:28:31,587 INFO OK: read value = false
2026-02-02 10:28:31,587 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru5_cfar_px_ctrl is equal to false
2026-02-02 10:28:31,588 INFO OK: read value = false
2026-02-02 10:28:31,588 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru6_timer is equal to false
2026-02-02 10:28:31,588 INFO OK: read value = false
2026-02-02 10:28:31,588 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru7_post_processor is equal to false
2026-02-02 10:28:31,588 INFO OK: read value = false
2026-02-02 10:28:31,588 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru8_agc is equal to false
2026-02-02 10:28:31,588 INFO OK: read value = false
2026-02-02 10:28:31,589 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru9_esa_if is equal to false
2026-02-02 10:28:31,589 INFO OK: read value = false
2026-02-02 10:28:31,589 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru1_chassis is equal to false
2026-02-02 10:28:31,589 INFO OK: read value = false
2026-02-02 10:28:31,590 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru2_uhf_assy is equal to false
2026-02-02 10:28:31,590 INFO OK: read value = false
2026-02-02 10:28:31,590 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru3_synthesizer is equal to false
2026-02-02 10:28:31,590 INFO OK: read value = false
2026-02-02 10:28:31,590 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru4_delta_guard_down_converter is equal to false
2026-02-02 10:28:31,590 INFO OK: read value = false
2026-02-02 10:28:31,591 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru5_sum_down_converter is equal to false
2026-02-02 10:28:31,591 INFO OK: read value = false
2026-02-02 10:28:31,591 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru6_lo_distributor is equal to false
2026-02-02 10:28:31,591 INFO OK: read value = false
2026-02-02 10:28:31,592 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru7_up_converter is equal to false
2026-02-02 10:28:31,593 INFO OK: read value = false
2026-02-02 10:28:31,594 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru1_chassis is equal to false
2026-02-02 10:28:31,594 INFO OK: read value = false
2026-02-02 10:28:31,594 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru2_delta_guard_lna is equal to false
2026-02-02 10:28:31,594 INFO OK: read value = false
2026-02-02 10:28:31,595 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru3_sum_act_prot_lna is equal to false
2026-02-02 10:28:31,595 INFO OK: read value = false
2026-02-02 10:28:31,595 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru4_4port_circulator is equal to false
2026-02-02 10:28:31,595 INFO OK: read value = false
2026-02-02 10:28:31,596 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_delta_guard is equal to false
2026-02-02 10:28:31,596 INFO OK: read value = false
2026-02-02 10:28:31,596 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_sum is equal to false
2026-02-02 10:28:31,597 INFO OK: read value = false
2026-02-02 10:28:31,597 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru1_chassis is equal to false
2026-02-02 10:28:31,597 INFO OK: read value = false
2026-02-02 10:28:31,597 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru2_power_supply is equal to false
2026-02-02 10:28:31,597 INFO OK: read value = false
2026-02-02 10:28:31,597 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru3_digital_controller is equal to false
2026-02-02 10:28:31,598 INFO OK: read value = false
2026-02-02 10:28:31,598 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru1_chassis is equal to false
2026-02-02 10:28:31,598 INFO OK: read value = false
2026-02-02 10:28:31,598 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru2_rex_f_tx is equal to false
2026-02-02 10:28:31,598 INFO OK: read value = false
2026-02-02 10:28:31,598 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru3_power_supply is equal to false
2026-02-02 10:28:31,598 INFO OK: read value = false
2026-02-02 10:28:31,598 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru4_valve_el_twt_tx is equal to false
2026-02-02 10:28:31,599 INFO OK: read value = false
2026-02-02 10:28:31,600 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru5_rf_driver is equal to false
2026-02-02 10:28:31,600 INFO OK: read value = false
2026-02-02 10:28:31,600 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru6_controller_tx is equal to false
2026-02-02 10:28:31,600 INFO OK: read value = false
2026-02-02 10:28:31,600 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru7_hv_power_supply is equal to false
2026-02-02 10:28:31,600 INFO OK: read value = false
2026-02-02 10:28:31,600 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru8_eht_power_supply is equal to false
2026-02-02 10:28:31,601 INFO OK: read value = false
2026-02-02 10:28:31,601 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc10_pulse_compressor_interface is equal to false
2026-02-02 10:28:31,601 INFO OK: read value = false
2026-02-02 10:28:31,601 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc11_dp_interface is equal to false
2026-02-02 10:28:31,601 INFO OK: read value = false
2026-02-02 10:28:31,601 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc13_taxi_running is equal to false
2026-02-02 10:28:31,602 INFO OK: read value = false
2026-02-02 10:28:31,602 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc14_external_xyp_ram is equal to false
2026-02-02 10:28:31,602 INFO OK: read value = false
2026-02-02 10:28:31,603 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc15_servoloop_interface is equal to false
2026-02-02 10:28:31,603 INFO OK: read value = false
2026-02-02 10:28:31,603 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc1_internal_xyp_ram is equal to false
2026-02-02 10:28:31,603 INFO OK: read value = false
2026-02-02 10:28:31,603 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc2_external_xyp_ram is equal to false
2026-02-02 10:28:31,604 INFO OK: read value = false
2026-02-02 10:28:31,604 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc5_dual_port_ram is equal to false
2026-02-02 10:28:31,604 INFO OK: read value = false
2026-02-02 10:28:31,604 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc6_agc_machine is equal to false
2026-02-02 10:28:31,605 INFO OK: read value = false
2026-02-02 10:28:31,605 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc7_sat_machine is equal to false
2026-02-02 10:28:31,605 INFO OK: read value = false
2026-02-02 10:28:31,606 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc9_c_ram_xy_checksum is equal to false
2026-02-02 10:28:31,606 INFO OK: read value = false
2026-02-02 10:28:31,606 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp10_video_memory is equal to false
2026-02-02 10:28:31,606 INFO OK: read value = false
2026-02-02 10:28:31,606 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp11_video_unit is equal to false
2026-02-02 10:28:31,607 INFO OK: read value = false
2026-02-02 10:28:31,607 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp12_transputer_unit is equal to false
2026-02-02 10:28:31,608 INFO OK: read value = false
2026-02-02 10:28:31,608 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp13_scan_converter_polar_memory is equal to false
2026-02-02 10:28:31,608 INFO OK: read value = false
2026-02-02 10:28:31,608 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp14_scan_converter_format_converter is equal to false
2026-02-02 10:28:31,608 INFO OK: read value = false
2026-02-02 10:28:31,609 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp1_486_cpu_tests is equal to false
2026-02-02 10:28:31,609 INFO OK: read value = false
2026-02-02 10:28:31,609 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp2_486_interfaces_with_r3000_gc is equal to false
2026-02-02 10:28:31,610 INFO OK: read value = false
2026-02-02 10:28:31,610 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp3_486_interface_with_slc is equal to false
2026-02-02 10:28:31,610 INFO OK: read value = false
2026-02-02 10:28:31,610 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp4_slc_communications is equal to false
2026-02-02 10:28:31,610 INFO OK: read value = false
2026-02-02 10:28:31,610 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp5_r3000_cpu_tests is equal to false
2026-02-02 10:28:31,611 INFO OK: read value = false
2026-02-02 10:28:31,611 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp6_r3000_interfaces is equal to false
2026-02-02 10:28:31,611 INFO OK: read value = false
2026-02-02 10:28:31,611 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp7_1553_and_discretes is equal to false
2026-02-02 10:28:31,612 INFO OK: read value = false
2026-02-02 10:28:31,612 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp8_graphic_cpu is equal to false
2026-02-02 10:28:31,612 INFO OK: read value = false
2026-02-02 10:28:31,612 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp9_graphic_processors is equal to false
2026-02-02 10:28:31,612 INFO OK: read value = false
2026-02-02 10:28:31,613 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_array_status is equal to false
2026-02-02 10:28:31,613 INFO OK: read value = false
2026-02-02 10:28:31,613 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_delta_channel_fail is equal to false
2026-02-02 10:28:31,613 INFO OK: read value = false
2026-02-02 10:28:31,613 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_injection_fail is equal to false
2026-02-02 10:28:31,613 INFO OK: read value = false
2026-02-02 10:28:31,614 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_noise_fail is equal to false
2026-02-02 10:28:31,614 INFO OK: read value = false
2026-02-02 10:28:31,614 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_pedestal_status is equal to false
2026-02-02 10:28:31,614 INFO OK: read value = false
2026-02-02 10:28:31,614 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_processor_status is equal to false
2026-02-02 10:28:31,614 INFO OK: read value = false
2026-02-02 10:28:31,615 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_receiver_status is equal to false
2026-02-02 10:28:31,615 INFO OK: read value = false
2026-02-02 10:28:31,615 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_rx_frontend_status is equal to false
2026-02-02 10:28:31,615 INFO OK: read value = false
2026-02-02 10:28:31,615 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_servoloop_status is equal to false
2026-02-02 10:28:31,615 INFO OK: read value = false
2026-02-02 10:28:31,615 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is1_upconverter_chain_levels is equal to false
2026-02-02 10:28:31,615 INFO OK: read value = false
2026-02-02 10:28:31,616 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is2_downconverter_chain_levels is equal to false
2026-02-02 10:28:31,616 INFO OK: read value = false
2026-02-02 10:28:31,616 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is3_antenna_status_inconsistent is equal to false
2026-02-02 10:28:31,616 INFO OK: read value = false
2026-02-02 10:28:31,616 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is4_tx_status_inconsistent is equal to false
2026-02-02 10:28:31,616 INFO OK: read value = false
2026-02-02 10:28:31,616 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is5_tx_power_level is equal to false
2026-02-02 10:28:31,616 INFO OK: read value = false
2026-02-02 10:28:31,616 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_transmitter_status is equal to false
2026-02-02 10:28:31,617 INFO OK: read value = false
2026-02-02 10:28:31,617 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp1_master_dsp is equal to false
2026-02-02 10:28:31,618 INFO OK: read value = false
2026-02-02 10:28:31,618 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp2_interface_card is equal to false
2026-02-02 10:28:31,618 INFO OK: read value = false
2026-02-02 10:28:31,618 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp3_cpu_cards is equal to false
2026-02-02 10:28:31,619 INFO OK: read value = false
2026-02-02 10:28:31,619 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp4_dma_bus is equal to false
2026-02-02 10:28:31,619 INFO OK: read value = false
2026-02-02 10:28:31,619 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp5_sp_interface is equal to false
2026-02-02 10:28:31,619 INFO OK: read value = false
2026-02-02 10:28:31,620 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp6_dp_interface is equal to false
2026-02-02 10:28:31,620 INFO OK: read value = false
2026-02-02 10:28:31,620 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp7_scan_converter_interface is equal to false
2026-02-02 10:28:31,620 INFO OK: read value = false
2026-02-02 10:28:31,620 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp8_agc_interface is equal to false
2026-02-02 10:28:31,621 INFO OK: read value = false
2026-02-02 10:28:31,621 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps1_power_supply is equal to false
2026-02-02 10:28:31,621 INFO OK: read value = false
2026-02-02 10:28:31,621 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps2_over_temperature is equal to false
2026-02-02 10:28:31,622 INFO OK: read value = false
2026-02-02 10:28:31,622 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe1_lna is equal to false
2026-02-02 10:28:31,622 INFO OK: read value = false
2026-02-02 10:28:31,623 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe2_agc_attenuators is equal to false
2026-02-02 10:28:31,623 INFO OK: read value = false
2026-02-02 10:28:31,630 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx1_synthesizer_commands is equal to false
2026-02-02 10:28:31,633 INFO OK: read value = false
2026-02-02 10:28:31,635 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx2_synthesizer_internal_tests is equal to false
2026-02-02 10:28:31,635 INFO OK: read value = false
2026-02-02 10:28:31,636 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx3_uhf_oscillator_level is equal to false
2026-02-02 10:28:31,636 INFO OK: read value = false
2026-02-02 10:28:31,637 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx4_downconverter_lo_level is equal to false
2026-02-02 10:28:31,637 INFO OK: read value = false
2026-02-02 10:28:31,637 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx5_upconverter_lo_level is equal to false
2026-02-02 10:28:31,637 INFO OK: read value = false
2026-02-02 10:28:31,638 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm16_calibration_sum_channel_fail is equal to false
2026-02-02 10:28:31,638 INFO OK: read value = false
2026-02-02 10:28:31,638 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm1_master_clock_level is equal to false
2026-02-02 10:28:31,638 INFO OK: read value = false
2026-02-02 10:28:31,638 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm2_expander_level is equal to false
2026-02-02 10:28:31,639 INFO OK: read value = false
2026-02-02 10:28:31,639 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm3_sum_channel_down_converter is equal to false
2026-02-02 10:28:31,639 INFO OK: read value = false
2026-02-02 10:28:31,639 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm4_dg_channel_down_converter is equal to false
2026-02-02 10:28:31,639 INFO OK: read value = false
2026-02-02 10:28:31,640 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm5_noise_attenuators is equal to false
2026-02-02 10:28:31,640 INFO OK: read value = false
2026-02-02 10:28:31,640 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl10_agc_control is equal to false
2026-02-02 10:28:31,640 INFO OK: read value = false
2026-02-02 10:28:31,640 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl11_ad is equal to false
2026-02-02 10:28:31,640 INFO OK: read value = false
2026-02-02 10:28:31,640 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl12_das is equal to false
2026-02-02 10:28:31,641 INFO OK: read value = false
2026-02-02 10:28:31,641 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl13_serial_communications is equal to false
2026-02-02 10:28:31,641 INFO OK: read value = false
2026-02-02 10:28:31,641 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl14_taxi_interface is equal to false
2026-02-02 10:28:31,641 INFO OK: read value = false
2026-02-02 10:28:31,641 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl15_pedestal_centre_scan_location is equal to false
2026-02-02 10:28:31,642 INFO OK: read value = false
2026-02-02 10:28:31,642 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl1_low_voltage_power_supply is equal to false
2026-02-02 10:28:31,642 INFO OK: read value = false
2026-02-02 10:28:31,642 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl2_high_voltage_power_supply is equal to false
2026-02-02 10:28:31,642 INFO OK: read value = false
2026-02-02 10:28:31,642 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl3_motor_drivers is equal to false
2026-02-02 10:28:31,642 INFO OK: read value = false
2026-02-02 10:28:31,642 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl4_resolvers_power_supply is equal to false
2026-02-02 10:28:31,643 INFO OK: read value = false
2026-02-02 10:28:31,643 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl5_waveguide_switch is equal to false
2026-02-02 10:28:31,643 INFO OK: read value = false
2026-02-02 10:28:31,643 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl6_over_temperature is equal to false
2026-02-02 10:28:31,643 INFO OK: read value = false
2026-02-02 10:28:31,643 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl7_resolver_to_digital_conv is equal to false
2026-02-02 10:28:31,643 INFO OK: read value = false
2026-02-02 10:28:31,644 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl8_position_loop_error is equal to false
2026-02-02 10:28:31,644 INFO OK: read value = false
2026-02-02 10:28:31,644 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl9_microprocessor is equal to false
2026-02-02 10:28:31,644 INFO OK: read value = false
2026-02-02 10:28:31,644 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp10_board_overall is equal to false
2026-02-02 10:28:31,644 INFO OK: read value = false
2026-02-02 10:28:31,645 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp11_attenuatori_antenna is equal to false
2026-02-02 10:28:31,645 INFO OK: read value = false
2026-02-02 10:28:31,645 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp14_external_sp_if is equal to false
2026-02-02 10:28:31,645 INFO OK: read value = false
2026-02-02 10:28:31,645 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp16_bcn is equal to false
2026-02-02 10:28:31,645 INFO OK: read value = false
2026-02-02 10:28:31,645 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp1_timer1_up is equal to false
2026-02-02 10:28:31,645 INFO OK: read value = false
2026-02-02 10:28:31,646 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp2_timer_dma_pxc_if is equal to false
2026-02-02 10:28:31,646 INFO OK: read value = false
2026-02-02 10:28:31,646 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp3_timer_internal is equal to false
2026-02-02 10:28:31,646 INFO OK: read value = false
2026-02-02 10:28:31,646 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp4_px_ctrl_comm is equal to false
2026-02-02 10:28:31,646 INFO OK: read value = false
2026-02-02 10:28:31,646 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp5_video1_without_ad is equal to false
2026-02-02 10:28:31,646 INFO OK: read value = false
2026-02-02 10:28:31,647 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp6_video1_with_ad is equal to false
2026-02-02 10:28:31,647 INFO OK: read value = false
2026-02-02 10:28:31,647 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp7_video2_ad_sync is equal to false
2026-02-02 10:28:31,647 INFO OK: read value = false
2026-02-02 10:28:31,647 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp8_video2_timer_sync is equal to false
2026-02-02 10:28:31,647 INFO OK: read value = false
2026-02-02 10:28:31,647 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9_ad_da is equal to false
2026-02-02 10:28:31,647 INFO OK: read value = false
2026-02-02 10:28:31,647 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9b_wideband_expander is equal to false
2026-02-02 10:28:31,648 INFO OK: read value = false
2026-02-02 10:28:31,648 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx10_hv_ps_over_temperature_warning is equal to false
2026-02-02 10:28:31,648 INFO OK: read value = false
2026-02-02 10:28:31,648 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx11_twt_helix_over_current is equal to false
2026-02-02 10:28:31,648 INFO OK: read value = false
2026-02-02 10:28:31,648 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx12_cathode_to_helix_arc is equal to false
2026-02-02 10:28:31,649 INFO OK: read value = false
2026-02-02 10:28:31,649 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx13_twt_over_temperature_hazard is equal to false
2026-02-02 10:28:31,649 INFO OK: read value = false
2026-02-02 10:28:31,649 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx14_twt_over_temperature_warning is equal to false
2026-02-02 10:28:31,649 INFO OK: read value = false
2026-02-02 10:28:31,649 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx15_cathode_under_voltage is equal to false
2026-02-02 10:28:31,650 INFO OK: read value = false
2026-02-02 10:28:31,650 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx16_cathode_over_voltage is equal to false
2026-02-02 10:28:31,650 INFO OK: read value = false
2026-02-02 10:28:31,650 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx1_microprocessors is equal to false
2026-02-02 10:28:31,650 INFO OK: read value = false
2026-02-02 10:28:31,650 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx2_tx_rf_input is equal to false
2026-02-02 10:28:31,650 INFO OK: read value = false
2026-02-02 10:28:31,650 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx3_twt_rf_input is equal to false
2026-02-02 10:28:31,651 INFO OK: read value = false
2026-02-02 10:28:31,651 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx4_twt_rf_output is equal to false
2026-02-02 10:28:31,651 INFO OK: read value = false
2026-02-02 10:28:31,651 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx5_tx_rf_output_level is equal to false
2026-02-02 10:28:31,651 INFO OK: read value = false
2026-02-02 10:28:31,651 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx6_vswr is equal to false
2026-02-02 10:28:31,651 INFO OK: read value = false
2026-02-02 10:28:31,652 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx7_three_phase_input_power is equal to false
2026-02-02 10:28:31,652 INFO OK: read value = false
2026-02-02 10:28:31,652 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx8_low_voltage_power_supplies is equal to false
2026-02-02 10:28:31,652 INFO OK: read value = false
2026-02-02 10:28:31,652 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx9_hv_ps_over_temperature_hazard is equal to false
2026-02-02 10:28:31,652 INFO OK: read value = false
2026-02-02 10:28:31,652 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx17_collector_under_voltage is equal to false
2026-02-02 10:28:31,652 INFO OK: read value = false
2026-02-02 10:28:31,652 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx18_collector_over_voltage is equal to false
2026-02-02 10:28:31,653 INFO OK: read value = false
2026-02-02 10:28:31,653 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx19_rectified_voltage is equal to false
2026-02-02 10:28:31,653 INFO OK: read value = false
2026-02-02 10:28:31,653 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx20_cathode_inv_current_fail is equal to false
2026-02-02 10:28:31,653 INFO OK: read value = false
2026-02-02 10:28:31,653 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx21_collector_inv_current_fail is equal to false
2026-02-02 10:28:31,653 INFO OK: read value = false
2026-02-02 10:28:31,654 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx22_waveguide_pressurization is equal to false
2026-02-02 10:28:31,654 INFO OK: read value = false
2026-02-02 10:28:31,654 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx23_grid_window_over_duty_alt is equal to false
2026-02-02 10:28:31,654 INFO OK: read value = false
2026-02-02 10:28:31,654 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx24_floating_deck_fail is equal to false
2026-02-02 10:28:31,654 INFO OK: read value = false
2026-02-02 10:28:31,655 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx25_floating_deck_ps_fail is equal to false
2026-02-02 10:28:31,655 INFO OK: read value = false
2026-02-02 10:28:31,655 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx26_grid_window_over_duty is equal to false
2026-02-02 10:28:31,656 INFO OK: read value = false
2026-02-02 10:28:31,656 INFO [Run 2] B8 Diagnostics: 173 checked, 172 pass, 1 fail
2026-02-02 10:28:31,657 WARNING B8_Degradation: 1 failures - fail
2026-02-02 10:28:31,657 INFO 0.0s remaining ...
2026-02-02 10:28:31,658 INFO [Run 2] Serial: 3 total, 0 errors, 3 fatal, 3 recycles
2026-02-02 10:28:31,660 WARNING Session: GRIFO_M_PBIT : Repetition 2 of 3
Total Step 189: Success 185 (97.88%), Failed 4 (2.12%),
2026-02-02 10:28:31,660 INFO Repetition 3 of 3
2026-02-02 10:28:31,661 DEBUG [MOCK] Serial statistics reset
2026-02-02 10:28:31,661 INFO The test operator is required to switch off the target and wait 3 seconds.
2026-02-02 10:28:32,661 INFO Set MAIN_POWER to False
2026-02-02 10:28:32,662 INFO [MOCK] Power OFF
2026-02-02 10:28:32,663 INFO [MOCK] 1553 Interface stopped
2026-02-02 10:28:37,664 INFO Check that MAIN_POWER is equal to 0
2026-02-02 10:28:37,664 INFO OK: read value = False
2026-02-02 10:28:41,665 INFO The test operator is required to switch on the target.
2026-02-02 10:28:41,665 INFO Set MAIN_POWER to True
2026-02-02 10:28:41,665 INFO [MOCK] Power ON
2026-02-02 10:28:41,666 INFO
====================================================================================================
[CRITICAL DEBUG] _initialize_field_values() CALLED
====================================================================================================
2026-02-02 10:28:41,666 INFO run_count = 3
2026-02-02 10:28:41,666 INFO SIMULATION_SCENARIO = 'mixed'
2026-02-02 10:28:41,666 INFO current_scenario = 'mixed'
2026-02-02 10:28:41,666 INFO _scenario_list = ['normal', 'recycle_fail_3', 'normal']
2026-02-02 10:28:41,666 INFO [DEBUG] Entering MIXED MODE branch
2026-02-02 10:28:41,667 INFO [DEBUG] Mixed mode: scenario_index=2, selected scenario='normal'
2026-02-02 10:28:41,667 INFO [DEBUG] About to call _log_scenario_info('normal', 3, 3)
2026-02-02 10:28:41,667 INFO
2026-02-02 10:28:41,667 INFO ####################################################################################################
2026-02-02 10:28:41,667 INFO ####################################################################################################
2026-02-02 10:28:41,667 INFO ### RUN 3/3: NORMAL OPERATION
2026-02-02 10:28:41,667 INFO ####################################################################################################
2026-02-02 10:28:41,668 INFO
2026-02-02 10:28:41,668 INFO SCENARIO: normal
2026-02-02 10:28:41,668 INFO DESCRIPTION: All systems operational - no failures
2026-02-02 10:28:41,668 INFO
2026-02-02 10:28:41,668 INFO EXPECTED FAILURES:
2026-02-02 10:28:41,668 INFO (none)
2026-02-02 10:28:41,668 INFO
2026-02-02 10:28:41,668 INFO EXPECTED PASSES:
2026-02-02 10:28:41,668 INFO ✓ All B6 status fields (except pedestal)
2026-02-02 10:28:41,669 INFO ✓ All B8 diagnostic fields
2026-02-02 10:28:41,669 INFO ✓ Target generation
2026-02-02 10:28:41,669 INFO
2026-02-02 10:28:41,669 INFO NOTES: Pedestal always fails due to HW test setup limitation (unit not present)
2026-02-02 10:28:41,669 INFO
2026-02-02 10:28:41,669 INFO ####################################################################################################
2026-02-02 10:28:41,669 INFO ####################################################################################################
2026-02-02 10:28:41,670 INFO
2026-02-02 10:28:41,670 INFO [DEBUG] _log_scenario_info() completed
2026-02-02 10:28:41,670 INFO [MOCK APPLY] ✓ All systems nominal (no failures injected)
2026-02-02 10:28:41,670 INFO [MOCK RECYCLE] Initial processor failure detected
2026-02-02 10:28:42,171 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:42,171 INFO [MOCK RECYCLE] RECYCLE 1/3 - NO RECOVERY
2026-02-02 10:28:42,672 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:42,672 INFO [MOCK RECYCLE] RECYCLE 2/3 - NO RECOVERY
2026-02-02 10:28:43,172 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 10:28:43,173 INFO [MOCK RECYCLE] RECYCLE 3/3 - NO RECOVERY
2026-02-02 10:28:43,173 WARNING [MOCK RECYCLE] System did NOT recover after 3 RECYCLEs - requires power cycle
2026-02-02 10:28:43,173 INFO [MOCK] 1553 Interface started - simulating BIT execution (Run 3)
2026-02-02 10:28:48,173 INFO Check that MAIN_POWER is equal to 1
2026-02-02 10:28:48,174 INFO OK: read value = True
2026-02-02 10:28:48,274 INFO [MOCK] BIT report available after 6.6s
2026-02-02 10:28:48,295 INFO BIT report available after 0.0s
2026-02-02 10:28:48,296 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_array_status is equal to false
2026-02-02 10:28:48,296 INFO OK: read value = false
2026-02-02 10:28:48,296 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status is equal to false
2026-02-02 10:28:48,297 WARNING CHECK ERROR: read value = true
2026-02-02 10:28:48,297 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 10:28:48,297 WARNING Known failure (ignored): radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status
2026-02-02 10:28:48,297 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pressurization_status is equal to false
2026-02-02 10:28:48,297 INFO OK: read value = false
2026-02-02 10:28:48,298 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_over_temperature_alarm is equal to false
2026-02-02 10:28:48,298 INFO OK: read value = false
2026-02-02 10:28:48,298 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_status is equal to false
2026-02-02 10:28:48,298 WARNING CHECK ERROR: read value = true
2026-02-02 10:28:48,298 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 10:28:48,298 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_receiver_status is equal to false
2026-02-02 10:28:48,299 INFO OK: read value = false
2026-02-02 10:28:48,299 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_rx_front_end_status is equal to false
2026-02-02 10:28:48,299 INFO OK: read value = false
2026-02-02 10:28:48,299 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_over_temperature_alarm is equal to false
2026-02-02 10:28:48,299 INFO OK: read value = false
2026-02-02 10:28:48,300 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_status is equal to false
2026-02-02 10:28:48,300 INFO OK: read value = false
2026-02-02 10:28:48,300 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_over_temperature_alarm is equal to false
2026-02-02 10:28:48,300 INFO OK: read value = false
2026-02-02 10:28:48,301 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_status is equal to false
2026-02-02 10:28:48,301 INFO OK: read value = false
2026-02-02 10:28:48,301 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_radar_fail_status is equal to false
2026-02-02 10:28:48,301 WARNING CHECK ERROR: read value = RDR_FAIL
2026-02-02 10:28:48,301 ERROR INTERFACE ERROR: Expected false, got RDR_FAIL
2026-02-02 10:28:48,301 WARNING Radar fail status: REAL failure (caused by: status, status)
2026-02-02 10:28:48,301 INFO [Run 3] B6 LRU Status: 12 total, 9 pass, 2 fail, 1 known
2026-02-02 10:28:48,302 INFO Known failures (HW setup): 1
2026-02-02 10:28:48,302 WARNING Real failures: status, status
2026-02-02 10:28:48,302 INFO
Drill-down: Verifying all 173 B8 diagnostic fields...
2026-02-02 10:28:48,302 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_bcn_fail is equal to false
2026-02-02 10:28:48,302 INFO OK: read value = false
2026-02-02 10:28:48,302 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_gm_rbm_sea1_ta_wa_fail is equal to false
2026-02-02 10:28:48,302 INFO OK: read value = false
2026-02-02 10:28:48,302 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group1_fail is equal to false
2026-02-02 10:28:48,302 INFO OK: read value = false
2026-02-02 10:28:48,302 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group2_fail is equal to false
2026-02-02 10:28:48,303 INFO OK: read value = false
2026-02-02 10:28:48,303 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group3_fail is equal to false
2026-02-02 10:28:48,303 INFO OK: read value = false
2026-02-02 10:28:48,303 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group4_fail is equal to false
2026-02-02 10:28:48,303 INFO OK: read value = false
2026-02-02 10:28:48,303 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group5_fail is equal to false
2026-02-02 10:28:48,303 INFO OK: read value = false
2026-02-02 10:28:48,303 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_hr_modes_and_gm_dbs_fail is equal to false
2026-02-02 10:28:48,303 INFO OK: read value = false
2026-02-02 10:28:48,304 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_no_rdr_symbology is equal to false
2026-02-02 10:28:48,304 INFO OK: read value = false
2026-02-02 10:28:48,304 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_not_identified_rdr_fail is equal to false
2026-02-02 10:28:48,304 WARNING CHECK ERROR: read value = 0
2026-02-02 10:28:48,304 ERROR INTERFACE ERROR: Expected false, got 0
2026-02-02 10:28:48,304 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_selected_channel_fail is equal to false
2026-02-02 10:28:48,304 INFO OK: read value = false
2026-02-02 10:28:48,304 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_total_rdr_fail is equal to false
2026-02-02 10:28:48,304 INFO OK: read value = false
2026-02-02 10:28:48,305 WARNING B8_Degradation: 1/12 failures
2026-02-02 10:28:48,305 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru1_gimbal is equal to false
2026-02-02 10:28:48,305 INFO OK: read value = false
2026-02-02 10:28:48,305 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru2_waveguide is equal to false
2026-02-02 10:28:48,305 INFO OK: read value = false
2026-02-02 10:28:48,305 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru3_waveguide is equal to false
2026-02-02 10:28:48,306 INFO OK: read value = false
2026-02-02 10:28:48,306 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru4_delta_guard_lna_switch is equal to false
2026-02-02 10:28:48,306 INFO OK: read value = false
2026-02-02 10:28:48,306 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru5_waveguide_switch is equal to false
2026-02-02 10:28:48,306 INFO OK: read value = false
2026-02-02 10:28:48,306 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru10_main_computer is equal to false
2026-02-02 10:28:48,306 INFO OK: read value = false
2026-02-02 10:28:48,306 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru11_graphic_computer is equal to false
2026-02-02 10:28:48,307 INFO OK: read value = false
2026-02-02 10:28:48,307 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru12_power_supply is equal to false
2026-02-02 10:28:48,307 INFO OK: read value = false
2026-02-02 10:28:48,307 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru13_det_exp is equal to false
2026-02-02 10:28:48,307 INFO OK: read value = false
2026-02-02 10:28:48,307 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru14_rx_module is equal to false
2026-02-02 10:28:48,307 INFO OK: read value = false
2026-02-02 10:28:48,308 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru1_motherboard_chassis is equal to false
2026-02-02 10:28:48,308 INFO OK: read value = false
2026-02-02 10:28:48,308 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru2_mti_fft is equal to false
2026-02-02 10:28:48,308 INFO OK: read value = false
2026-02-02 10:28:48,308 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru3_dsp0 is equal to false
2026-02-02 10:28:48,308 INFO OK: read value = false
2026-02-02 10:28:48,309 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru4_dsp1 is equal to false
2026-02-02 10:28:48,309 INFO OK: read value = false
2026-02-02 10:28:48,309 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru5_cfar_px_ctrl is equal to false
2026-02-02 10:28:48,309 INFO OK: read value = false
2026-02-02 10:28:48,309 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru6_timer is equal to false
2026-02-02 10:28:48,310 INFO OK: read value = false
2026-02-02 10:28:48,310 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru7_post_processor is equal to false
2026-02-02 10:28:48,310 INFO OK: read value = false
2026-02-02 10:28:48,310 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru8_agc is equal to false
2026-02-02 10:28:48,311 INFO OK: read value = false
2026-02-02 10:28:48,311 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru9_esa_if is equal to false
2026-02-02 10:28:48,311 INFO OK: read value = false
2026-02-02 10:28:48,311 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru1_chassis is equal to false
2026-02-02 10:28:48,311 INFO OK: read value = false
2026-02-02 10:28:48,311 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru2_uhf_assy is equal to false
2026-02-02 10:28:48,311 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru3_synthesizer is equal to false
2026-02-02 10:28:48,312 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru4_delta_guard_down_converter is equal to false
2026-02-02 10:28:48,312 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru5_sum_down_converter is equal to false
2026-02-02 10:28:48,312 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru6_lo_distributor is equal to false
2026-02-02 10:28:48,312 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru7_up_converter is equal to false
2026-02-02 10:28:48,312 INFO OK: read value = false
2026-02-02 10:28:48,312 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru1_chassis is equal to false
2026-02-02 10:28:48,313 INFO OK: read value = false
2026-02-02 10:28:48,313 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru2_delta_guard_lna is equal to false
2026-02-02 10:28:48,313 INFO OK: read value = false
2026-02-02 10:28:48,313 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru3_sum_act_prot_lna is equal to false
2026-02-02 10:28:48,313 INFO OK: read value = false
2026-02-02 10:28:48,313 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru4_4port_circulator is equal to false
2026-02-02 10:28:48,313 INFO OK: read value = false
2026-02-02 10:28:48,313 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_delta_guard is equal to false
2026-02-02 10:28:48,314 INFO OK: read value = false
2026-02-02 10:28:48,314 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_sum is equal to false
2026-02-02 10:28:48,314 INFO OK: read value = false
2026-02-02 10:28:48,314 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru1_chassis is equal to false
2026-02-02 10:28:48,314 INFO OK: read value = false
2026-02-02 10:28:48,314 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru2_power_supply is equal to false
2026-02-02 10:28:48,314 INFO OK: read value = false
2026-02-02 10:28:48,314 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru3_digital_controller is equal to false
2026-02-02 10:28:48,314 INFO OK: read value = false
2026-02-02 10:28:48,314 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru1_chassis is equal to false
2026-02-02 10:28:48,315 INFO OK: read value = false
2026-02-02 10:28:48,315 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru2_rex_f_tx is equal to false
2026-02-02 10:28:48,315 INFO OK: read value = false
2026-02-02 10:28:48,315 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru3_power_supply is equal to false
2026-02-02 10:28:48,315 INFO OK: read value = false
2026-02-02 10:28:48,315 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru4_valve_el_twt_tx is equal to false
2026-02-02 10:28:48,315 INFO OK: read value = false
2026-02-02 10:28:48,316 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru5_rf_driver is equal to false
2026-02-02 10:28:48,316 INFO OK: read value = false
2026-02-02 10:28:48,316 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru6_controller_tx is equal to false
2026-02-02 10:28:48,316 INFO OK: read value = false
2026-02-02 10:28:48,316 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru7_hv_power_supply is equal to false
2026-02-02 10:28:48,316 INFO OK: read value = false
2026-02-02 10:28:48,316 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru8_eht_power_supply is equal to false
2026-02-02 10:28:48,316 INFO OK: read value = false
2026-02-02 10:28:48,316 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc10_pulse_compressor_interface is equal to false
2026-02-02 10:28:48,317 INFO OK: read value = false
2026-02-02 10:28:48,317 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc11_dp_interface is equal to false
2026-02-02 10:28:48,318 INFO OK: read value = false
2026-02-02 10:28:48,318 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc13_taxi_running is equal to false
2026-02-02 10:28:48,318 INFO OK: read value = false
2026-02-02 10:28:48,318 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc14_external_xyp_ram is equal to false
2026-02-02 10:28:48,318 INFO OK: read value = false
2026-02-02 10:28:48,318 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc15_servoloop_interface is equal to false
2026-02-02 10:28:48,319 INFO OK: read value = false
2026-02-02 10:28:48,319 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc1_internal_xyp_ram is equal to false
2026-02-02 10:28:48,319 INFO OK: read value = false
2026-02-02 10:28:48,319 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc2_external_xyp_ram is equal to false
2026-02-02 10:28:48,320 INFO OK: read value = false
2026-02-02 10:28:48,320 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc5_dual_port_ram is equal to false
2026-02-02 10:28:48,321 INFO OK: read value = false
2026-02-02 10:28:48,321 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc6_agc_machine is equal to false
2026-02-02 10:28:48,321 INFO OK: read value = false
2026-02-02 10:28:48,321 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc7_sat_machine is equal to false
2026-02-02 10:28:48,321 INFO OK: read value = false
2026-02-02 10:28:48,321 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc9_c_ram_xy_checksum is equal to false
2026-02-02 10:28:48,321 INFO OK: read value = false
2026-02-02 10:28:48,322 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp10_video_memory is equal to false
2026-02-02 10:28:48,322 INFO OK: read value = false
2026-02-02 10:28:48,322 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp11_video_unit is equal to false
2026-02-02 10:28:48,322 INFO OK: read value = false
2026-02-02 10:28:48,322 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp12_transputer_unit is equal to false
2026-02-02 10:28:48,323 INFO OK: read value = false
2026-02-02 10:28:48,323 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp13_scan_converter_polar_memory is equal to false
2026-02-02 10:28:48,323 INFO OK: read value = false
2026-02-02 10:28:48,323 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp14_scan_converter_format_converter is equal to false
2026-02-02 10:28:48,324 INFO OK: read value = false
2026-02-02 10:28:48,324 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp1_486_cpu_tests is equal to false
2026-02-02 10:28:48,325 INFO OK: read value = false
2026-02-02 10:28:48,326 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp2_486_interfaces_with_r3000_gc is equal to false
2026-02-02 10:28:48,327 INFO OK: read value = false
2026-02-02 10:28:48,328 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp3_486_interface_with_slc is equal to false
2026-02-02 10:28:48,328 INFO OK: read value = false
2026-02-02 10:28:48,328 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp4_slc_communications is equal to false
2026-02-02 10:28:48,328 INFO OK: read value = false
2026-02-02 10:28:48,328 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp5_r3000_cpu_tests is equal to false
2026-02-02 10:28:48,329 INFO OK: read value = false
2026-02-02 10:28:48,329 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp6_r3000_interfaces is equal to false
2026-02-02 10:28:48,329 INFO OK: read value = false
2026-02-02 10:28:48,329 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp7_1553_and_discretes is equal to false
2026-02-02 10:28:48,330 INFO OK: read value = false
2026-02-02 10:28:48,331 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp8_graphic_cpu is equal to false
2026-02-02 10:28:48,331 INFO OK: read value = false
2026-02-02 10:28:48,332 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp9_graphic_processors is equal to false
2026-02-02 10:28:48,333 INFO OK: read value = false
2026-02-02 10:28:48,333 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_array_status is equal to false
2026-02-02 10:28:48,333 INFO OK: read value = false
2026-02-02 10:28:48,333 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_delta_channel_fail is equal to false
2026-02-02 10:28:48,334 INFO OK: read value = false
2026-02-02 10:28:48,334 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_injection_fail is equal to false
2026-02-02 10:28:48,334 INFO OK: read value = false
2026-02-02 10:28:48,335 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_noise_fail is equal to false
2026-02-02 10:28:48,335 INFO OK: read value = false
2026-02-02 10:28:48,336 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_pedestal_status is equal to false
2026-02-02 10:28:48,336 INFO OK: read value = false
2026-02-02 10:28:48,336 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_processor_status is equal to false
2026-02-02 10:28:48,336 INFO OK: read value = false
2026-02-02 10:28:48,336 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_receiver_status is equal to false
2026-02-02 10:28:48,337 INFO OK: read value = false
2026-02-02 10:28:48,337 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_rx_frontend_status is equal to false
2026-02-02 10:28:48,337 INFO OK: read value = false
2026-02-02 10:28:48,337 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_servoloop_status is equal to false
2026-02-02 10:28:48,337 INFO OK: read value = false
2026-02-02 10:28:48,338 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is1_upconverter_chain_levels is equal to false
2026-02-02 10:28:48,338 INFO OK: read value = false
2026-02-02 10:28:48,338 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is2_downconverter_chain_levels is equal to false
2026-02-02 10:28:48,338 INFO OK: read value = false
2026-02-02 10:28:48,338 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is3_antenna_status_inconsistent is equal to false
2026-02-02 10:28:48,338 INFO OK: read value = false
2026-02-02 10:28:48,338 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is4_tx_status_inconsistent is equal to false
2026-02-02 10:28:48,338 INFO OK: read value = false
2026-02-02 10:28:48,339 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is5_tx_power_level is equal to false
2026-02-02 10:28:48,339 INFO OK: read value = false
2026-02-02 10:28:48,339 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_transmitter_status is equal to false
2026-02-02 10:28:48,339 INFO OK: read value = false
2026-02-02 10:28:48,340 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp1_master_dsp is equal to false
2026-02-02 10:28:48,340 INFO OK: read value = false
2026-02-02 10:28:48,340 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp2_interface_card is equal to false
2026-02-02 10:28:48,340 INFO OK: read value = false
2026-02-02 10:28:48,341 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp3_cpu_cards is equal to false
2026-02-02 10:28:48,343 INFO OK: read value = false
2026-02-02 10:28:48,344 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp4_dma_bus is equal to false
2026-02-02 10:28:48,344 INFO OK: read value = false
2026-02-02 10:28:48,344 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp5_sp_interface is equal to false
2026-02-02 10:28:48,345 INFO OK: read value = false
2026-02-02 10:28:48,345 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp6_dp_interface is equal to false
2026-02-02 10:28:48,345 INFO OK: read value = false
2026-02-02 10:28:48,345 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp7_scan_converter_interface is equal to false
2026-02-02 10:28:48,345 INFO OK: read value = false
2026-02-02 10:28:48,345 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp8_agc_interface is equal to false
2026-02-02 10:28:48,345 INFO OK: read value = false
2026-02-02 10:28:48,346 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps1_power_supply is equal to false
2026-02-02 10:28:48,346 INFO OK: read value = false
2026-02-02 10:28:48,347 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps2_over_temperature is equal to false
2026-02-02 10:28:48,347 INFO OK: read value = false
2026-02-02 10:28:48,347 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe1_lna is equal to false
2026-02-02 10:28:48,348 INFO OK: read value = false
2026-02-02 10:28:48,350 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe2_agc_attenuators is equal to false
2026-02-02 10:28:48,351 INFO OK: read value = false
2026-02-02 10:28:48,351 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx1_synthesizer_commands is equal to false
2026-02-02 10:28:48,352 INFO OK: read value = false
2026-02-02 10:28:48,353 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx2_synthesizer_internal_tests is equal to false
2026-02-02 10:28:48,353 INFO OK: read value = false
2026-02-02 10:28:48,354 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx3_uhf_oscillator_level is equal to false
2026-02-02 10:28:48,355 INFO OK: read value = false
2026-02-02 10:28:48,355 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx4_downconverter_lo_level is equal to false
2026-02-02 10:28:48,355 INFO OK: read value = false
2026-02-02 10:28:48,355 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx5_upconverter_lo_level is equal to false
2026-02-02 10:28:48,356 INFO OK: read value = false
2026-02-02 10:28:48,356 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm16_calibration_sum_channel_fail is equal to false
2026-02-02 10:28:48,356 INFO OK: read value = false
2026-02-02 10:28:48,357 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm1_master_clock_level is equal to false
2026-02-02 10:28:48,357 INFO OK: read value = false
2026-02-02 10:28:48,357 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm2_expander_level is equal to false
2026-02-02 10:28:48,358 INFO OK: read value = false
2026-02-02 10:28:48,358 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm3_sum_channel_down_converter is equal to false
2026-02-02 10:28:48,358 INFO OK: read value = false
2026-02-02 10:28:48,358 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm4_dg_channel_down_converter is equal to false
2026-02-02 10:28:48,358 INFO OK: read value = false
2026-02-02 10:28:48,359 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm5_noise_attenuators is equal to false
2026-02-02 10:28:48,359 INFO OK: read value = false
2026-02-02 10:28:48,359 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl10_agc_control is equal to false
2026-02-02 10:28:48,359 INFO OK: read value = false
2026-02-02 10:28:48,359 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl11_ad is equal to false
2026-02-02 10:28:48,359 INFO OK: read value = false
2026-02-02 10:28:48,359 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl12_das is equal to false
2026-02-02 10:28:48,359 INFO OK: read value = false
2026-02-02 10:28:48,359 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl13_serial_communications is equal to false
2026-02-02 10:28:48,360 INFO OK: read value = false
2026-02-02 10:28:48,360 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl14_taxi_interface is equal to false
2026-02-02 10:28:48,360 INFO OK: read value = false
2026-02-02 10:28:48,360 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl15_pedestal_centre_scan_location is equal to false
2026-02-02 10:28:48,360 INFO OK: read value = false
2026-02-02 10:28:48,360 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl1_low_voltage_power_supply is equal to false
2026-02-02 10:28:48,360 INFO OK: read value = false
2026-02-02 10:28:48,361 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl2_high_voltage_power_supply is equal to false
2026-02-02 10:28:48,361 INFO OK: read value = false
2026-02-02 10:28:48,361 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl3_motor_drivers is equal to false
2026-02-02 10:28:48,361 INFO OK: read value = false
2026-02-02 10:28:48,361 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl4_resolvers_power_supply is equal to false
2026-02-02 10:28:48,361 INFO OK: read value = false
2026-02-02 10:28:48,361 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl5_waveguide_switch is equal to false
2026-02-02 10:28:48,362 INFO OK: read value = false
2026-02-02 10:28:48,362 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl6_over_temperature is equal to false
2026-02-02 10:28:48,362 INFO OK: read value = false
2026-02-02 10:28:48,362 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl7_resolver_to_digital_conv is equal to false
2026-02-02 10:28:48,362 INFO OK: read value = false
2026-02-02 10:28:48,362 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl8_position_loop_error is equal to false
2026-02-02 10:28:48,362 INFO OK: read value = false
2026-02-02 10:28:48,362 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl9_microprocessor is equal to false
2026-02-02 10:28:48,362 INFO OK: read value = false
2026-02-02 10:28:48,363 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp10_board_overall is equal to false
2026-02-02 10:28:48,363 INFO OK: read value = false
2026-02-02 10:28:48,363 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp11_attenuatori_antenna is equal to false
2026-02-02 10:28:48,363 INFO OK: read value = false
2026-02-02 10:28:48,363 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp14_external_sp_if is equal to false
2026-02-02 10:28:48,363 INFO OK: read value = false
2026-02-02 10:28:48,364 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp16_bcn is equal to false
2026-02-02 10:28:48,364 INFO OK: read value = false
2026-02-02 10:28:48,364 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp1_timer1_up is equal to false
2026-02-02 10:28:48,364 INFO OK: read value = false
2026-02-02 10:28:48,364 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp2_timer_dma_pxc_if is equal to false
2026-02-02 10:28:48,364 INFO OK: read value = false
2026-02-02 10:28:48,364 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp3_timer_internal is equal to false
2026-02-02 10:28:48,365 INFO OK: read value = false
2026-02-02 10:28:48,365 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp4_px_ctrl_comm is equal to false
2026-02-02 10:28:48,365 INFO OK: read value = false
2026-02-02 10:28:48,365 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp5_video1_without_ad is equal to false
2026-02-02 10:28:48,365 INFO OK: read value = false
2026-02-02 10:28:48,365 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp6_video1_with_ad is equal to false
2026-02-02 10:28:48,365 INFO OK: read value = false
2026-02-02 10:28:48,366 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp7_video2_ad_sync is equal to false
2026-02-02 10:28:48,366 INFO OK: read value = false
2026-02-02 10:28:48,366 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp8_video2_timer_sync is equal to false
2026-02-02 10:28:48,366 INFO OK: read value = false
2026-02-02 10:28:48,367 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9_ad_da is equal to false
2026-02-02 10:28:48,367 INFO OK: read value = false
2026-02-02 10:28:48,367 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9b_wideband_expander is equal to false
2026-02-02 10:28:48,367 INFO OK: read value = false
2026-02-02 10:28:48,367 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx10_hv_ps_over_temperature_warning is equal to false
2026-02-02 10:28:48,367 INFO OK: read value = false
2026-02-02 10:28:48,367 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx11_twt_helix_over_current is equal to false
2026-02-02 10:28:48,368 INFO OK: read value = false
2026-02-02 10:28:48,368 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx12_cathode_to_helix_arc is equal to false
2026-02-02 10:28:48,368 INFO OK: read value = false
2026-02-02 10:28:48,368 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx13_twt_over_temperature_hazard is equal to false
2026-02-02 10:28:48,368 INFO OK: read value = false
2026-02-02 10:28:48,368 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx14_twt_over_temperature_warning is equal to false
2026-02-02 10:28:48,369 INFO OK: read value = false
2026-02-02 10:28:48,369 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx15_cathode_under_voltage is equal to false
2026-02-02 10:28:48,369 INFO OK: read value = false
2026-02-02 10:28:48,369 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx16_cathode_over_voltage is equal to false
2026-02-02 10:28:48,369 INFO OK: read value = false
2026-02-02 10:28:48,370 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx1_microprocessors is equal to false
2026-02-02 10:28:48,370 INFO OK: read value = false
2026-02-02 10:28:48,370 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx2_tx_rf_input is equal to false
2026-02-02 10:28:48,370 INFO OK: read value = false
2026-02-02 10:28:48,370 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx3_twt_rf_input is equal to false
2026-02-02 10:28:48,370 INFO OK: read value = false
2026-02-02 10:28:48,371 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx4_twt_rf_output is equal to false
2026-02-02 10:28:48,371 INFO OK: read value = false
2026-02-02 10:28:48,371 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx5_tx_rf_output_level is equal to false
2026-02-02 10:28:48,371 INFO OK: read value = false
2026-02-02 10:28:48,371 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx6_vswr is equal to false
2026-02-02 10:28:48,371 INFO OK: read value = false
2026-02-02 10:28:48,372 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx7_three_phase_input_power is equal to false
2026-02-02 10:28:48,372 INFO OK: read value = false
2026-02-02 10:28:48,372 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx8_low_voltage_power_supplies is equal to false
2026-02-02 10:28:48,372 INFO OK: read value = false
2026-02-02 10:28:48,372 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx9_hv_ps_over_temperature_hazard is equal to false
2026-02-02 10:28:48,372 INFO OK: read value = false
2026-02-02 10:28:48,373 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx17_collector_under_voltage is equal to false
2026-02-02 10:28:48,373 INFO OK: read value = false
2026-02-02 10:28:48,373 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx18_collector_over_voltage is equal to false
2026-02-02 10:28:48,373 INFO OK: read value = false
2026-02-02 10:28:48,373 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx19_rectified_voltage is equal to false
2026-02-02 10:28:48,373 INFO OK: read value = false
2026-02-02 10:28:48,374 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx20_cathode_inv_current_fail is equal to false
2026-02-02 10:28:48,374 INFO OK: read value = false
2026-02-02 10:28:48,374 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx21_collector_inv_current_fail is equal to false
2026-02-02 10:28:48,374 INFO OK: read value = false
2026-02-02 10:28:48,374 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx22_waveguide_pressurization is equal to false
2026-02-02 10:28:48,374 INFO OK: read value = false
2026-02-02 10:28:48,375 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx23_grid_window_over_duty_alt is equal to false
2026-02-02 10:28:48,375 INFO OK: read value = false
2026-02-02 10:28:48,375 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx24_floating_deck_fail is equal to false
2026-02-02 10:28:48,375 INFO OK: read value = false
2026-02-02 10:28:48,376 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx25_floating_deck_ps_fail is equal to false
2026-02-02 10:28:48,376 INFO OK: read value = false
2026-02-02 10:28:48,376 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx26_grid_window_over_duty is equal to false
2026-02-02 10:28:48,376 INFO OK: read value = false
2026-02-02 10:28:48,377 INFO [Run 3] B8 Diagnostics: 173 checked, 172 pass, 1 fail
2026-02-02 10:28:48,377 WARNING B8_Degradation: 1 failures - fail
2026-02-02 10:28:48,377 INFO 0.0s remaining ...
2026-02-02 10:28:48,377 INFO [Run 3] Serial: 3 total, 0 errors, 3 fatal, 3 recycles
2026-02-02 10:28:48,378 WARNING Session: GRIFO_M_PBIT : Repetition 3 of 3
Total Step 189: Success 185 (97.88%), Failed 4 (2.12%),
2026-02-02 10:28:48,378 INFO tgt_gen()
2026-02-02 10:28:48,389 INFO TgtMsg: 1 1
2026-02-02 10:28:48,389 INFO Tgt: 1 @ 1180
2026-02-02 10:28:48,389 INFO Check that B9 b9_t_num is between 1 and 2
2026-02-02 10:28:48,389 INFO OK: read value = 1
2026-02-02 10:28:48,390 INFO Check that B9 b9_t1_rng is between 1179 and 1186
2026-02-02 10:28:48,390 INFO OK: read value = 1180
2026-02-02 10:28:48,390 INFO Repetitions terminated.
2026-02-02 10:28:48,391 INFO [Report] Custom statistics data registered for PDF generation
2026-02-02 10:28:48,391 INFO ==========================================================================================
2026-02-02 10:28:48,391 INFO FINAL TEST STATISTICS SUMMARY
2026-02-02 10:28:48,391 INFO ==========================================================================================
2026-02-02 10:28:48,391 INFO Total Runs: 3
2026-02-02 10:28:48,392 INFO Successful: 1 (33.3%)
2026-02-02 10:28:48,392 INFO Failed: 2 (66.7%)
2026-02-02 10:28:48,392 INFO B6 Checks: 36 (Pass: 28, Fail: 4, Known: 4)
2026-02-02 10:28:48,392 INFO B8 Checks: 519 (Pass: 516, Fail: 3)
2026-02-02 10:28:48,393 INFO Serial: 6 messages (0 errors, 6 fatal, 6 recycles)
2026-02-02 10:28:48,393 INFO PBIT Timing: avg=0.02s, min=0.02s, max=0.02s, σ=0.00s
2026-02-02 10:28:48,393 INFO ==========================================================================================
2026-02-02 10:28:48,393 INFO Detailed statistics will be available in the PDF report
2026-02-02 10:28:48,393 INFO Exporting statistics to CSV: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_102848_statistics.csv
2026-02-02 10:28:48,406 INFO Statistics exported successfully to: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_102848_statistics.csv
2026-02-02 10:28:48,409 INFO Statistics exported successfully to JSON: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_102848_statistics.json
2026-02-02 10:28:48,410 INFO Set MAIN_POWER to False
2026-02-02 10:28:48,410 INFO [MOCK] Power OFF
2026-02-02 10:28:48,410 INFO [MOCK] 1553 Interface stopped
2026-02-02 10:28:53,411 INFO Check that MAIN_POWER is equal to 0
2026-02-02 10:28:53,413 INFO OK: read value = False
2026-02-02 10:28:53,413 INFO [MOCK] Serial terminal disconnected
2026-02-02 10:28:53,413 INFO Stop Time: 2026-02-02 10:27:59.685162
2026-02-02 10:28:53,414 INFO Test execution time: 0:00:53.728669