2026-02-02 14:18:07,837 INFO Start Time: 2026-02-02 14:18:07.837211
2026-02-02 14:18:07,838 INFO [MOCK] Serial terminal initialized
2026-02-02 14:18:07,838 INFO [MOCK] Serial terminal connected
2026-02-02 14:18:07,838 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 14:18:07,839 INFO The Test Operator check if the failure BIT in B6_MsgRdrSettingsAndParametersTellback changes ...
2026-02-02 14:18:07,839 INFO [MOCK] Log started at level 3 in directory: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts
2026-02-02 14:18:07,840 INFO tgt_gen_alone(): 0
2026-02-02 14:18:07,840 INFO tgt_gen()
2026-02-02 14:18:07,865 WARNING [MOCK] getSingleMessageReceivedSz called but interface not started! Returning 0
2026-02-02 14:18:07,865 INFO TgtMsg: 0 0
2026-02-02 14:18:07,866 INFO Tgt: 1 @ 1180
2026-02-02 14:18:07,866 INFO Check that B9 b9_t_num is between 1 and 2
2026-02-02 14:18:07,866 INFO OK: read value = 1
2026-02-02 14:18:07,866 INFO Check that B9 b9_t1_rng is between 1179 and 1186
2026-02-02 14:18:07,867 INFO OK: read value = 1180
2026-02-02 14:18:07,867 INFO [MOCK] Log stopped
2026-02-02 14:18:07,867 INFO Repetition 1 of 2
2026-02-02 14:18:07,867 DEBUG [MOCK] Serial statistics reset
2026-02-02 14:18:07,867 INFO The test operator is required to switch off the target and wait 3 seconds.
2026-02-02 14:18:08,869 INFO Set MAIN_POWER to False
2026-02-02 14:18:08,869 INFO [MOCK] Power OFF
2026-02-02 14:18:08,869 INFO [MOCK] 1553 Interface stopped
2026-02-02 14:18:13,878 INFO Check that MAIN_POWER is equal to 0
2026-02-02 14:18:13,878 INFO OK: read value = False
2026-02-02 14:18:17,889 INFO The test operator is required to switch on the target.
2026-02-02 14:18:17,891 INFO Set MAIN_POWER to True
2026-02-02 14:18:17,893 INFO [MOCK] Power ON
2026-02-02 14:18:17,894 INFO
====================================================================================================
[CRITICAL DEBUG] _initialize_field_values() CALLED
====================================================================================================
2026-02-02 14:18:17,895 INFO run_count = 1
2026-02-02 14:18:17,896 INFO SIMULATION_SCENARIO = 'mixed'
2026-02-02 14:18:17,896 INFO current_scenario = 'mixed'
2026-02-02 14:18:17,897 INFO _scenario_list = ['normal', 'recycle_fail_3']
2026-02-02 14:18:17,898 INFO [DEBUG] Entering MIXED MODE branch
2026-02-02 14:18:17,898 INFO [DEBUG] Mixed mode: scenario_index=0, selected scenario='normal'
2026-02-02 14:18:17,899 INFO [DEBUG] About to call _log_scenario_info('normal', 1, 2)
2026-02-02 14:18:17,899 INFO
2026-02-02 14:18:17,899 INFO ####################################################################################################
2026-02-02 14:18:17,900 INFO ####################################################################################################
2026-02-02 14:18:17,900 INFO ### RUN 1/2: NORMAL OPERATION
2026-02-02 14:18:17,900 INFO ####################################################################################################
2026-02-02 14:18:17,900 INFO
2026-02-02 14:18:17,901 INFO SCENARIO: normal
2026-02-02 14:18:17,901 INFO DESCRIPTION: All systems operational - no failures
2026-02-02 14:18:17,901 INFO
2026-02-02 14:18:17,902 INFO EXPECTED FAILURES:
2026-02-02 14:18:17,903 INFO (none)
2026-02-02 14:18:17,903 INFO
2026-02-02 14:18:17,908 INFO EXPECTED PASSES:
2026-02-02 14:18:17,908 INFO ✓ All B6 status fields (except pedestal)
2026-02-02 14:18:17,908 INFO ✓ All B8 diagnostic fields
2026-02-02 14:18:17,908 INFO ✓ Target generation
2026-02-02 14:18:17,909 INFO
2026-02-02 14:18:17,909 INFO NOTES: Pedestal always fails due to HW test setup limitation (unit not present)
2026-02-02 14:18:17,912 INFO
2026-02-02 14:18:17,913 INFO ####################################################################################################
2026-02-02 14:18:17,913 INFO ####################################################################################################
2026-02-02 14:18:17,913 INFO
2026-02-02 14:18:17,914 INFO [DEBUG] _log_scenario_info() completed
2026-02-02 14:18:17,914 INFO [MOCK APPLY] ✓ All systems nominal (no failures injected)
2026-02-02 14:18:17,914 INFO [MOCK] 1553 Interface started - simulating BIT execution (Run 1)
2026-02-02 14:18:22,919 INFO Check that MAIN_POWER is equal to 1
2026-02-02 14:18:22,920 INFO OK: read value = True
2026-02-02 14:18:23,027 INFO Set A1_MsgRdrSettingsAndParameters settings_RDROperationalSettings_rdr_symbology_intensity to 100
2026-02-02 14:18:23,231 INFO [MOCK] BIT report available after 5.3s
2026-02-02 14:18:23,262 INFO BIT report available after 0.2s
2026-02-02 14:18:23,262 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_array_status is equal to false
2026-02-02 14:18:23,263 INFO OK: read value = false
2026-02-02 14:18:23,263 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status is equal to false
2026-02-02 14:18:23,263 WARNING CHECK ERROR: read value = true
2026-02-02 14:18:23,263 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 14:18:23,263 WARNING Known failure (ignored): radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status
2026-02-02 14:18:23,263 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pressurization_status is equal to false
2026-02-02 14:18:23,264 INFO OK: read value = false
2026-02-02 14:18:23,264 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_over_temperature_alarm is equal to false
2026-02-02 14:18:23,264 INFO OK: read value = false
2026-02-02 14:18:23,264 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_status is equal to false
2026-02-02 14:18:23,264 INFO OK: read value = false
2026-02-02 14:18:23,264 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_receiver_status is equal to false
2026-02-02 14:18:23,264 INFO OK: read value = false
2026-02-02 14:18:23,265 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_rx_front_end_status is equal to false
2026-02-02 14:18:23,265 INFO OK: read value = false
2026-02-02 14:18:23,265 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_over_temperature_alarm is equal to false
2026-02-02 14:18:23,265 INFO OK: read value = false
2026-02-02 14:18:23,265 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_status is equal to false
2026-02-02 14:18:23,265 INFO OK: read value = false
2026-02-02 14:18:23,265 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_over_temperature_alarm is equal to false
2026-02-02 14:18:23,266 INFO OK: read value = false
2026-02-02 14:18:23,266 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_status is equal to false
2026-02-02 14:18:23,266 INFO OK: read value = false
2026-02-02 14:18:23,266 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_radar_fail_status is equal to false
2026-02-02 14:18:23,266 WARNING CHECK ERROR: read value = RDR_OK
2026-02-02 14:18:23,266 ERROR INTERFACE ERROR: Expected false, got RDR_OK
2026-02-02 14:18:23,267 WARNING Radar fail status: Known failure (caused only by pedestal)
2026-02-02 14:18:23,267 INFO [Run 1] B6 LRU Status: 12 total, 10 pass, 0 fail, 2 known
2026-02-02 14:18:23,267 INFO Known failures (HW setup): 2
2026-02-02 14:18:23,267 INFO
Forced B8 drill-down (FORCE_B8_DRILL_DOWN=True): Verifying all 173 B8 diagnostic fields...
2026-02-02 14:18:23,267 INFO [FORCE_B8_DRILL_DOWN] Performing B8 drill-down despite only known failures
2026-02-02 14:18:23,267 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_bcn_fail is equal to false
2026-02-02 14:18:23,268 INFO OK: read value = false
2026-02-02 14:18:23,268 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_gm_rbm_sea1_ta_wa_fail is equal to false
2026-02-02 14:18:23,268 INFO OK: read value = false
2026-02-02 14:18:23,269 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group1_fail is equal to false
2026-02-02 14:18:23,269 INFO OK: read value = false
2026-02-02 14:18:23,269 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group2_fail is equal to false
2026-02-02 14:18:23,269 INFO OK: read value = false
2026-02-02 14:18:23,269 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group3_fail is equal to false
2026-02-02 14:18:23,269 INFO OK: read value = false
2026-02-02 14:18:23,269 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group4_fail is equal to false
2026-02-02 14:18:23,270 INFO OK: read value = false
2026-02-02 14:18:23,270 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group5_fail is equal to false
2026-02-02 14:18:23,270 INFO OK: read value = false
2026-02-02 14:18:23,270 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_hr_modes_and_gm_dbs_fail is equal to false
2026-02-02 14:18:23,270 INFO OK: read value = false
2026-02-02 14:18:23,270 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_no_rdr_symbology is equal to false
2026-02-02 14:18:23,270 INFO OK: read value = false
2026-02-02 14:18:23,270 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_not_identified_rdr_fail is equal to false
2026-02-02 14:18:23,271 WARNING CHECK ERROR: read value = 0
2026-02-02 14:18:23,271 ERROR INTERFACE ERROR: Expected false, got 0
2026-02-02 14:18:23,271 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_selected_channel_fail is equal to false
2026-02-02 14:18:23,271 INFO OK: read value = false
2026-02-02 14:18:23,271 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_total_rdr_fail is equal to false
2026-02-02 14:18:23,271 INFO OK: read value = false
2026-02-02 14:18:23,272 WARNING B8_Degradation: 1/12 failures
2026-02-02 14:18:23,272 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru1_gimbal is equal to false
2026-02-02 14:18:23,272 INFO OK: read value = false
2026-02-02 14:18:23,272 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru2_waveguide is equal to false
2026-02-02 14:18:23,272 INFO OK: read value = false
2026-02-02 14:18:23,272 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru3_waveguide is equal to false
2026-02-02 14:18:23,272 INFO OK: read value = false
2026-02-02 14:18:23,273 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru4_delta_guard_lna_switch is equal to false
2026-02-02 14:18:23,273 INFO OK: read value = false
2026-02-02 14:18:23,273 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru5_waveguide_switch is equal to false
2026-02-02 14:18:23,273 INFO OK: read value = false
2026-02-02 14:18:23,273 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru10_main_computer is equal to false
2026-02-02 14:18:23,273 INFO OK: read value = false
2026-02-02 14:18:23,273 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru11_graphic_computer is equal to false
2026-02-02 14:18:23,274 INFO OK: read value = false
2026-02-02 14:18:23,274 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru12_power_supply is equal to false
2026-02-02 14:18:23,274 INFO OK: read value = false
2026-02-02 14:18:23,274 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru13_det_exp is equal to false
2026-02-02 14:18:23,274 INFO OK: read value = false
2026-02-02 14:18:23,274 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru14_rx_module is equal to false
2026-02-02 14:18:23,274 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru1_motherboard_chassis is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru2_mti_fft is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru3_dsp0 is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru4_dsp1 is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru5_cfar_px_ctrl is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,275 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru6_timer is equal to false
2026-02-02 14:18:23,275 INFO OK: read value = false
2026-02-02 14:18:23,277 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru7_post_processor is equal to false
2026-02-02 14:18:23,277 INFO OK: read value = false
2026-02-02 14:18:23,277 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru8_agc is equal to false
2026-02-02 14:18:23,277 INFO OK: read value = false
2026-02-02 14:18:23,277 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru9_esa_if is equal to false
2026-02-02 14:18:23,277 INFO OK: read value = false
2026-02-02 14:18:23,278 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru1_chassis is equal to false
2026-02-02 14:18:23,278 INFO OK: read value = false
2026-02-02 14:18:23,278 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru2_uhf_assy is equal to false
2026-02-02 14:18:23,278 INFO OK: read value = false
2026-02-02 14:18:23,278 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru3_synthesizer is equal to false
2026-02-02 14:18:23,278 INFO OK: read value = false
2026-02-02 14:18:23,279 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru4_delta_guard_down_converter is equal to false
2026-02-02 14:18:23,279 INFO OK: read value = false
2026-02-02 14:18:23,279 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru5_sum_down_converter is equal to false
2026-02-02 14:18:23,279 INFO OK: read value = false
2026-02-02 14:18:23,279 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru6_lo_distributor is equal to false
2026-02-02 14:18:23,279 INFO OK: read value = false
2026-02-02 14:18:23,279 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru7_up_converter is equal to false
2026-02-02 14:18:23,280 INFO OK: read value = false
2026-02-02 14:18:23,280 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru1_chassis is equal to false
2026-02-02 14:18:23,280 INFO OK: read value = false
2026-02-02 14:18:23,280 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru2_delta_guard_lna is equal to false
2026-02-02 14:18:23,280 INFO OK: read value = false
2026-02-02 14:18:23,280 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru3_sum_act_prot_lna is equal to false
2026-02-02 14:18:23,280 INFO OK: read value = false
2026-02-02 14:18:23,281 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru4_4port_circulator is equal to false
2026-02-02 14:18:23,281 INFO OK: read value = false
2026-02-02 14:18:23,281 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_delta_guard is equal to false
2026-02-02 14:18:23,281 INFO OK: read value = false
2026-02-02 14:18:23,281 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_sum is equal to false
2026-02-02 14:18:23,281 INFO OK: read value = false
2026-02-02 14:18:23,281 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru1_chassis is equal to false
2026-02-02 14:18:23,281 INFO OK: read value = false
2026-02-02 14:18:23,282 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru2_power_supply is equal to false
2026-02-02 14:18:23,282 INFO OK: read value = false
2026-02-02 14:18:23,282 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru3_digital_controller is equal to false
2026-02-02 14:18:23,282 INFO OK: read value = false
2026-02-02 14:18:23,282 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru1_chassis is equal to false
2026-02-02 14:18:23,282 INFO OK: read value = false
2026-02-02 14:18:23,282 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru2_rex_f_tx is equal to false
2026-02-02 14:18:23,282 INFO OK: read value = false
2026-02-02 14:18:23,282 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru3_power_supply is equal to false
2026-02-02 14:18:23,282 INFO OK: read value = false
2026-02-02 14:18:23,283 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru4_valve_el_twt_tx is equal to false
2026-02-02 14:18:23,283 INFO OK: read value = false
2026-02-02 14:18:23,283 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru5_rf_driver is equal to false
2026-02-02 14:18:23,283 INFO OK: read value = false
2026-02-02 14:18:23,284 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru6_controller_tx is equal to false
2026-02-02 14:18:23,285 INFO OK: read value = false
2026-02-02 14:18:23,285 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru7_hv_power_supply is equal to false
2026-02-02 14:18:23,285 INFO OK: read value = false
2026-02-02 14:18:23,285 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru8_eht_power_supply is equal to false
2026-02-02 14:18:23,285 INFO OK: read value = false
2026-02-02 14:18:23,285 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc10_pulse_compressor_interface is equal to false
2026-02-02 14:18:23,285 INFO OK: read value = false
2026-02-02 14:18:23,286 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc11_dp_interface is equal to false
2026-02-02 14:18:23,286 INFO OK: read value = false
2026-02-02 14:18:23,286 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc13_taxi_running is equal to false
2026-02-02 14:18:23,286 INFO OK: read value = false
2026-02-02 14:18:23,286 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc14_external_xyp_ram is equal to false
2026-02-02 14:18:23,287 INFO OK: read value = false
2026-02-02 14:18:23,287 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc15_servoloop_interface is equal to false
2026-02-02 14:18:23,287 INFO OK: read value = false
2026-02-02 14:18:23,287 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc1_internal_xyp_ram is equal to false
2026-02-02 14:18:23,287 INFO OK: read value = false
2026-02-02 14:18:23,287 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc2_external_xyp_ram is equal to false
2026-02-02 14:18:23,287 INFO OK: read value = false
2026-02-02 14:18:23,288 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc5_dual_port_ram is equal to false
2026-02-02 14:18:23,288 INFO OK: read value = false
2026-02-02 14:18:23,288 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc6_agc_machine is equal to false
2026-02-02 14:18:23,288 INFO OK: read value = false
2026-02-02 14:18:23,289 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc7_sat_machine is equal to false
2026-02-02 14:18:23,293 INFO OK: read value = false
2026-02-02 14:18:23,293 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc9_c_ram_xy_checksum is equal to false
2026-02-02 14:18:23,294 INFO OK: read value = false
2026-02-02 14:18:23,294 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp10_video_memory is equal to false
2026-02-02 14:18:23,294 INFO OK: read value = false
2026-02-02 14:18:23,294 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp11_video_unit is equal to false
2026-02-02 14:18:23,294 INFO OK: read value = false
2026-02-02 14:18:23,294 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp12_transputer_unit is equal to false
2026-02-02 14:18:23,295 INFO OK: read value = false
2026-02-02 14:18:23,295 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp13_scan_converter_polar_memory is equal to false
2026-02-02 14:18:23,295 INFO OK: read value = false
2026-02-02 14:18:23,295 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp14_scan_converter_format_converter is equal to false
2026-02-02 14:18:23,295 INFO OK: read value = false
2026-02-02 14:18:23,295 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp1_486_cpu_tests is equal to false
2026-02-02 14:18:23,295 INFO OK: read value = false
2026-02-02 14:18:23,295 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp2_486_interfaces_with_r3000_gc is equal to false
2026-02-02 14:18:23,296 INFO OK: read value = false
2026-02-02 14:18:23,297 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp3_486_interface_with_slc is equal to false
2026-02-02 14:18:23,297 INFO OK: read value = false
2026-02-02 14:18:23,297 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp4_slc_communications is equal to false
2026-02-02 14:18:23,297 INFO OK: read value = false
2026-02-02 14:18:23,297 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp5_r3000_cpu_tests is equal to false
2026-02-02 14:18:23,297 INFO OK: read value = false
2026-02-02 14:18:23,297 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp6_r3000_interfaces is equal to false
2026-02-02 14:18:23,297 INFO OK: read value = false
2026-02-02 14:18:23,297 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp7_1553_and_discretes is equal to false
2026-02-02 14:18:23,297 INFO OK: read value = false
2026-02-02 14:18:23,298 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp8_graphic_cpu is equal to false
2026-02-02 14:18:23,298 INFO OK: read value = false
2026-02-02 14:18:23,298 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp9_graphic_processors is equal to false
2026-02-02 14:18:23,298 INFO OK: read value = false
2026-02-02 14:18:23,298 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_array_status is equal to false
2026-02-02 14:18:23,298 INFO OK: read value = false
2026-02-02 14:18:23,299 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_delta_channel_fail is equal to false
2026-02-02 14:18:23,299 INFO OK: read value = false
2026-02-02 14:18:23,299 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_injection_fail is equal to false
2026-02-02 14:18:23,299 INFO OK: read value = false
2026-02-02 14:18:23,299 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_noise_fail is equal to false
2026-02-02 14:18:23,299 INFO OK: read value = false
2026-02-02 14:18:23,299 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_pedestal_status is equal to false
2026-02-02 14:18:23,299 INFO OK: read value = false
2026-02-02 14:18:23,299 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_processor_status is equal to false
2026-02-02 14:18:23,300 INFO OK: read value = false
2026-02-02 14:18:23,300 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_receiver_status is equal to false
2026-02-02 14:18:23,300 INFO OK: read value = false
2026-02-02 14:18:23,300 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_rx_frontend_status is equal to false
2026-02-02 14:18:23,300 INFO OK: read value = false
2026-02-02 14:18:23,300 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_servoloop_status is equal to false
2026-02-02 14:18:23,300 INFO OK: read value = false
2026-02-02 14:18:23,300 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is1_upconverter_chain_levels is equal to false
2026-02-02 14:18:23,301 INFO OK: read value = false
2026-02-02 14:18:23,301 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is2_downconverter_chain_levels is equal to false
2026-02-02 14:18:23,301 INFO OK: read value = false
2026-02-02 14:18:23,301 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is3_antenna_status_inconsistent is equal to false
2026-02-02 14:18:23,301 INFO OK: read value = false
2026-02-02 14:18:23,301 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is4_tx_status_inconsistent is equal to false
2026-02-02 14:18:23,301 INFO OK: read value = false
2026-02-02 14:18:23,302 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is5_tx_power_level is equal to false
2026-02-02 14:18:23,302 INFO OK: read value = false
2026-02-02 14:18:23,302 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_transmitter_status is equal to false
2026-02-02 14:18:23,302 INFO OK: read value = false
2026-02-02 14:18:23,302 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp1_master_dsp is equal to false
2026-02-02 14:18:23,302 INFO OK: read value = false
2026-02-02 14:18:23,302 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp2_interface_card is equal to false
2026-02-02 14:18:23,303 INFO OK: read value = false
2026-02-02 14:18:23,303 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp3_cpu_cards is equal to false
2026-02-02 14:18:23,303 INFO OK: read value = false
2026-02-02 14:18:23,304 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp4_dma_bus is equal to false
2026-02-02 14:18:23,304 INFO OK: read value = false
2026-02-02 14:18:23,304 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp5_sp_interface is equal to false
2026-02-02 14:18:23,304 INFO OK: read value = false
2026-02-02 14:18:23,304 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp6_dp_interface is equal to false
2026-02-02 14:18:23,305 INFO OK: read value = false
2026-02-02 14:18:23,305 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp7_scan_converter_interface is equal to false
2026-02-02 14:18:23,305 INFO OK: read value = false
2026-02-02 14:18:23,305 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp8_agc_interface is equal to false
2026-02-02 14:18:23,305 INFO OK: read value = false
2026-02-02 14:18:23,306 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps1_power_supply is equal to false
2026-02-02 14:18:23,306 INFO OK: read value = false
2026-02-02 14:18:23,306 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps2_over_temperature is equal to false
2026-02-02 14:18:23,306 INFO OK: read value = false
2026-02-02 14:18:23,306 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe1_lna is equal to false
2026-02-02 14:18:23,306 INFO OK: read value = false
2026-02-02 14:18:23,307 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe2_agc_attenuators is equal to false
2026-02-02 14:18:23,307 INFO OK: read value = false
2026-02-02 14:18:23,307 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx1_synthesizer_commands is equal to false
2026-02-02 14:18:23,307 INFO OK: read value = false
2026-02-02 14:18:23,307 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx2_synthesizer_internal_tests is equal to false
2026-02-02 14:18:23,307 INFO OK: read value = false
2026-02-02 14:18:23,307 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx3_uhf_oscillator_level is equal to false
2026-02-02 14:18:23,307 INFO OK: read value = false
2026-02-02 14:18:23,307 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx4_downconverter_lo_level is equal to false
2026-02-02 14:18:23,309 INFO OK: read value = false
2026-02-02 14:18:23,309 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx5_upconverter_lo_level is equal to false
2026-02-02 14:18:23,309 INFO OK: read value = false
2026-02-02 14:18:23,309 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm16_calibration_sum_channel_fail is equal to false
2026-02-02 14:18:23,309 INFO OK: read value = false
2026-02-02 14:18:23,310 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm1_master_clock_level is equal to false
2026-02-02 14:18:23,310 INFO OK: read value = false
2026-02-02 14:18:23,310 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm2_expander_level is equal to false
2026-02-02 14:18:23,310 INFO OK: read value = false
2026-02-02 14:18:23,310 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm3_sum_channel_down_converter is equal to false
2026-02-02 14:18:23,310 INFO OK: read value = false
2026-02-02 14:18:23,311 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm4_dg_channel_down_converter is equal to false
2026-02-02 14:18:23,311 INFO OK: read value = false
2026-02-02 14:18:23,311 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm5_noise_attenuators is equal to false
2026-02-02 14:18:23,311 INFO OK: read value = false
2026-02-02 14:18:23,311 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl10_agc_control is equal to false
2026-02-02 14:18:23,311 INFO OK: read value = false
2026-02-02 14:18:23,311 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl11_ad is equal to false
2026-02-02 14:18:23,312 INFO OK: read value = false
2026-02-02 14:18:23,312 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl12_das is equal to false
2026-02-02 14:18:23,312 INFO OK: read value = false
2026-02-02 14:18:23,312 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl13_serial_communications is equal to false
2026-02-02 14:18:23,312 INFO OK: read value = false
2026-02-02 14:18:23,312 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl14_taxi_interface is equal to false
2026-02-02 14:18:23,312 INFO OK: read value = false
2026-02-02 14:18:23,313 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl15_pedestal_centre_scan_location is equal to false
2026-02-02 14:18:23,313 INFO OK: read value = false
2026-02-02 14:18:23,313 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl1_low_voltage_power_supply is equal to false
2026-02-02 14:18:23,314 INFO OK: read value = false
2026-02-02 14:18:23,314 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl2_high_voltage_power_supply is equal to false
2026-02-02 14:18:23,314 INFO OK: read value = false
2026-02-02 14:18:23,314 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl3_motor_drivers is equal to false
2026-02-02 14:18:23,314 INFO OK: read value = false
2026-02-02 14:18:23,314 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl4_resolvers_power_supply is equal to false
2026-02-02 14:18:23,314 INFO OK: read value = false
2026-02-02 14:18:23,314 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl5_waveguide_switch is equal to false
2026-02-02 14:18:23,314 INFO OK: read value = false
2026-02-02 14:18:23,314 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl6_over_temperature is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,315 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl7_resolver_to_digital_conv is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,315 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl8_position_loop_error is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,315 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl9_microprocessor is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,315 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp10_board_overall is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,315 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp11_attenuatori_antenna is equal to false
2026-02-02 14:18:23,315 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp14_external_sp_if is equal to false
2026-02-02 14:18:23,316 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp16_bcn is equal to false
2026-02-02 14:18:23,316 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp1_timer1_up is equal to false
2026-02-02 14:18:23,316 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp2_timer_dma_pxc_if is equal to false
2026-02-02 14:18:23,316 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp3_timer_internal is equal to false
2026-02-02 14:18:23,316 INFO OK: read value = false
2026-02-02 14:18:23,316 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp4_px_ctrl_comm is equal to false
2026-02-02 14:18:23,317 INFO OK: read value = false
2026-02-02 14:18:23,317 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp5_video1_without_ad is equal to false
2026-02-02 14:18:23,317 INFO OK: read value = false
2026-02-02 14:18:23,317 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp6_video1_with_ad is equal to false
2026-02-02 14:18:23,318 INFO OK: read value = false
2026-02-02 14:18:23,318 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp7_video2_ad_sync is equal to false
2026-02-02 14:18:23,318 INFO OK: read value = false
2026-02-02 14:18:23,318 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp8_video2_timer_sync is equal to false
2026-02-02 14:18:23,319 INFO OK: read value = false
2026-02-02 14:18:23,319 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9_ad_da is equal to false
2026-02-02 14:18:23,319 INFO OK: read value = false
2026-02-02 14:18:23,319 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9b_wideband_expander is equal to false
2026-02-02 14:18:23,319 INFO OK: read value = false
2026-02-02 14:18:23,319 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx10_hv_ps_over_temperature_warning is equal to false
2026-02-02 14:18:23,320 INFO OK: read value = false
2026-02-02 14:18:23,320 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx11_twt_helix_over_current is equal to false
2026-02-02 14:18:23,320 INFO OK: read value = false
2026-02-02 14:18:23,320 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx12_cathode_to_helix_arc is equal to false
2026-02-02 14:18:23,320 INFO OK: read value = false
2026-02-02 14:18:23,320 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx13_twt_over_temperature_hazard is equal to false
2026-02-02 14:18:23,321 INFO OK: read value = false
2026-02-02 14:18:23,321 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx14_twt_over_temperature_warning is equal to false
2026-02-02 14:18:23,321 INFO OK: read value = false
2026-02-02 14:18:23,321 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx15_cathode_under_voltage is equal to false
2026-02-02 14:18:23,321 INFO OK: read value = false
2026-02-02 14:18:23,322 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx16_cathode_over_voltage is equal to false
2026-02-02 14:18:23,322 INFO OK: read value = false
2026-02-02 14:18:23,322 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx1_microprocessors is equal to false
2026-02-02 14:18:23,322 INFO OK: read value = false
2026-02-02 14:18:23,322 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx2_tx_rf_input is equal to false
2026-02-02 14:18:23,322 INFO OK: read value = false
2026-02-02 14:18:23,322 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx3_twt_rf_input is equal to false
2026-02-02 14:18:23,323 INFO OK: read value = false
2026-02-02 14:18:23,323 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx4_twt_rf_output is equal to false
2026-02-02 14:18:23,323 INFO OK: read value = false
2026-02-02 14:18:23,323 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx5_tx_rf_output_level is equal to false
2026-02-02 14:18:23,323 INFO OK: read value = false
2026-02-02 14:18:23,323 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx6_vswr is equal to false
2026-02-02 14:18:23,323 INFO OK: read value = false
2026-02-02 14:18:23,323 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx7_three_phase_input_power is equal to false
2026-02-02 14:18:23,324 INFO OK: read value = false
2026-02-02 14:18:23,324 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx8_low_voltage_power_supplies is equal to false
2026-02-02 14:18:23,324 INFO OK: read value = false
2026-02-02 14:18:23,324 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx9_hv_ps_over_temperature_hazard is equal to false
2026-02-02 14:18:23,324 INFO OK: read value = false
2026-02-02 14:18:23,324 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx17_collector_under_voltage is equal to false
2026-02-02 14:18:23,324 INFO OK: read value = false
2026-02-02 14:18:23,325 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx18_collector_over_voltage is equal to false
2026-02-02 14:18:23,325 INFO OK: read value = false
2026-02-02 14:18:23,325 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx19_rectified_voltage is equal to false
2026-02-02 14:18:23,325 INFO OK: read value = false
2026-02-02 14:18:23,325 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx20_cathode_inv_current_fail is equal to false
2026-02-02 14:18:23,326 INFO OK: read value = false
2026-02-02 14:18:23,326 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx21_collector_inv_current_fail is equal to false
2026-02-02 14:18:23,326 INFO OK: read value = false
2026-02-02 14:18:23,327 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx22_waveguide_pressurization is equal to false
2026-02-02 14:18:23,327 INFO OK: read value = false
2026-02-02 14:18:23,327 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx23_grid_window_over_duty_alt is equal to false
2026-02-02 14:18:23,327 INFO OK: read value = false
2026-02-02 14:18:23,328 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx24_floating_deck_fail is equal to false
2026-02-02 14:18:23,328 INFO OK: read value = false
2026-02-02 14:18:23,328 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx25_floating_deck_ps_fail is equal to false
2026-02-02 14:18:23,328 INFO OK: read value = false
2026-02-02 14:18:23,328 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx26_grid_window_over_duty is equal to false
2026-02-02 14:18:23,328 INFO OK: read value = false
2026-02-02 14:18:23,329 INFO [Run 1] B8 Diagnostics: 173 checked, 172 pass, 1 fail
2026-02-02 14:18:23,329 WARNING B8_Degradation: 1 failures - fail
2026-02-02 14:18:23,329 INFO 0.0s remaining ...
2026-02-02 14:18:23,329 INFO [Run 1] Serial: 0 total, 0 errors, 0 fatal, 0 recycles
2026-02-02 14:18:23,329 WARNING Session: GRIFO_M_PBIT : Repetition 1 of 2
Total Step 192: Success 189 (98.44%), Failed 3 (1.56%),
2026-02-02 14:18:23,330 INFO Repetition 2 of 2
2026-02-02 14:18:23,330 DEBUG [MOCK] Serial statistics reset
2026-02-02 14:18:23,330 INFO The test operator is required to switch off the target and wait 3 seconds.
2026-02-02 14:18:24,343 INFO Set MAIN_POWER to False
2026-02-02 14:18:24,343 INFO [MOCK] Power OFF
2026-02-02 14:18:24,343 INFO [MOCK] 1553 Interface stopped
2026-02-02 14:18:29,346 INFO Check that MAIN_POWER is equal to 0
2026-02-02 14:18:29,346 INFO OK: read value = False
2026-02-02 14:18:33,363 INFO The test operator is required to switch on the target.
2026-02-02 14:18:33,363 INFO Set MAIN_POWER to True
2026-02-02 14:18:33,363 INFO [MOCK] Power ON
2026-02-02 14:18:33,363 INFO
====================================================================================================
[CRITICAL DEBUG] _initialize_field_values() CALLED
====================================================================================================
2026-02-02 14:18:33,363 INFO run_count = 2
2026-02-02 14:18:33,363 INFO SIMULATION_SCENARIO = 'mixed'
2026-02-02 14:18:33,363 INFO current_scenario = 'mixed'
2026-02-02 14:18:33,363 INFO _scenario_list = ['normal', 'recycle_fail_3']
2026-02-02 14:18:33,363 INFO [DEBUG] Entering MIXED MODE branch
2026-02-02 14:18:33,363 INFO [DEBUG] Mixed mode: scenario_index=1, selected scenario='recycle_fail_3'
2026-02-02 14:18:33,363 INFO [DEBUG] About to call _log_scenario_info('recycle_fail_3', 2, 2)
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO ####################################################################################################
2026-02-02 14:18:33,363 INFO ####################################################################################################
2026-02-02 14:18:33,363 INFO ### RUN 2/2: RECYCLE NO RECOVERY (3+ CYCLES)
2026-02-02 14:18:33,363 INFO ####################################################################################################
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO SCENARIO: recycle_fail_3
2026-02-02 14:18:33,363 INFO DESCRIPTION: Processor fails and NEVER recovers despite 3 RECYCLE events
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO EXPECTED FAILURES:
2026-02-02 14:18:33,363 INFO ✗ Persistent: processor_status = FAIL
2026-02-02 14:18:33,363 INFO ✗ Serial: 3x RECYCLE events detected
2026-02-02 14:18:33,363 INFO ✗ No recovery achieved
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO EXPECTED PASSES:
2026-02-02 14:18:33,363 INFO ✓ None - system remains in failed state
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO NOTES: Simulates hard failure requiring power cycle. Test should fail and report persistent failure
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO ####################################################################################################
2026-02-02 14:18:33,363 INFO ####################################################################################################
2026-02-02 14:18:33,363 INFO
2026-02-02 14:18:33,363 INFO [DEBUG] _log_scenario_info() completed
2026-02-02 14:18:33,363 INFO [MOCK APPLY] ⚠ RECYCLE scenario enabled: NO recovery (persistent failure)
2026-02-02 14:18:33,363 INFO [MOCK RECYCLE] Initial processor failure detected
2026-02-02 14:18:33,875 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 14:18:33,875 INFO [MOCK RECYCLE] RECYCLE 1/3 - NO RECOVERY
2026-02-02 14:18:34,375 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 14:18:34,375 INFO [MOCK RECYCLE] RECYCLE 2/3 - NO RECOVERY
2026-02-02 14:18:34,889 INFO [MOCK] Simulated RECYCLE event: %%F-10747-SP*: ***** RECYCLE!******
2026-02-02 14:18:34,889 INFO [MOCK RECYCLE] RECYCLE 3/3 - NO RECOVERY
2026-02-02 14:18:34,891 WARNING [MOCK RECYCLE] System did NOT recover after 3 RECYCLEs - requires power cycle
2026-02-02 14:18:34,891 INFO [MOCK] 1553 Interface started - simulating BIT execution (Run 2)
2026-02-02 14:18:39,900 INFO Check that MAIN_POWER is equal to 1
2026-02-02 14:18:39,900 INFO OK: read value = True
2026-02-02 14:18:40,010 INFO Set A1_MsgRdrSettingsAndParameters settings_RDROperationalSettings_rdr_symbology_intensity to 100
2026-02-02 14:18:40,211 INFO [MOCK] BIT report available after 6.8s
2026-02-02 14:18:40,242 INFO BIT report available after 0.2s
2026-02-02 14:18:40,242 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_array_status is equal to false
2026-02-02 14:18:40,242 INFO OK: read value = false
2026-02-02 14:18:40,243 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status is equal to false
2026-02-02 14:18:40,243 WARNING CHECK ERROR: read value = true
2026-02-02 14:18:40,243 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 14:18:40,243 WARNING Known failure (ignored): radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pedestal_status
2026-02-02 14:18:40,243 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_pressurization_status is equal to false
2026-02-02 14:18:40,244 INFO OK: read value = false
2026-02-02 14:18:40,245 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_over_temperature_alarm is equal to false
2026-02-02 14:18:40,247 INFO OK: read value = false
2026-02-02 14:18:40,247 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_processor_status is equal to false
2026-02-02 14:18:40,247 WARNING CHECK ERROR: read value = true
2026-02-02 14:18:40,247 ERROR INTERFACE ERROR: Expected false, got true
2026-02-02 14:18:40,247 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_receiver_status is equal to false
2026-02-02 14:18:40,247 INFO OK: read value = false
2026-02-02 14:18:40,248 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_rx_front_end_status is equal to false
2026-02-02 14:18:40,248 INFO OK: read value = false
2026-02-02 14:18:40,248 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_over_temperature_alarm is equal to false
2026-02-02 14:18:40,248 INFO OK: read value = false
2026-02-02 14:18:40,248 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_servoloop_status is equal to false
2026-02-02 14:18:40,249 INFO OK: read value = false
2026-02-02 14:18:40,249 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_over_temperature_alarm is equal to false
2026-02-02 14:18:40,249 INFO OK: read value = false
2026-02-02 14:18:40,249 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_trasmitter_status is equal to false
2026-02-02 14:18:40,249 INFO OK: read value = false
2026-02-02 14:18:40,250 INFO Check that B6_MsgRdrSettingsAndParametersTellback radar_health_status_and_bit_report_valid_RdrHealthStatusAndBitReport_radar_fail_status is equal to false
2026-02-02 14:18:40,250 WARNING CHECK ERROR: read value = RDR_FAIL
2026-02-02 14:18:40,250 ERROR INTERFACE ERROR: Expected false, got RDR_FAIL
2026-02-02 14:18:40,250 WARNING Radar fail status: REAL failure (caused by: status, status)
2026-02-02 14:18:40,250 INFO [Run 2] B6 LRU Status: 12 total, 9 pass, 2 fail, 1 known
2026-02-02 14:18:40,250 INFO Known failures (HW setup): 1
2026-02-02 14:18:40,251 WARNING Real failures: status, status
2026-02-02 14:18:40,251 INFO
Drill-down: Verifying all 173 B8 diagnostic fields...
2026-02-02 14:18:40,251 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_bcn_fail is equal to false
2026-02-02 14:18:40,251 INFO OK: read value = false
2026-02-02 14:18:40,251 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_gm_rbm_sea1_ta_wa_fail is equal to false
2026-02-02 14:18:40,251 INFO OK: read value = false
2026-02-02 14:18:40,251 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group1_fail is equal to false
2026-02-02 14:18:40,251 INFO OK: read value = false
2026-02-02 14:18:40,251 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group2_fail is equal to false
2026-02-02 14:18:40,251 INFO OK: read value = false
2026-02-02 14:18:40,251 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group3_fail is equal to false
2026-02-02 14:18:40,252 INFO OK: read value = false
2026-02-02 14:18:40,252 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group4_fail is equal to false
2026-02-02 14:18:40,252 INFO OK: read value = false
2026-02-02 14:18:40,252 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_group5_fail is equal to false
2026-02-02 14:18:40,252 INFO OK: read value = false
2026-02-02 14:18:40,252 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_hr_modes_and_gm_dbs_fail is equal to false
2026-02-02 14:18:40,253 INFO OK: read value = false
2026-02-02 14:18:40,253 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_no_rdr_symbology is equal to false
2026-02-02 14:18:40,253 INFO OK: read value = false
2026-02-02 14:18:40,253 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_not_identified_rdr_fail is equal to false
2026-02-02 14:18:40,254 WARNING CHECK ERROR: read value = 0
2026-02-02 14:18:40,254 ERROR INTERFACE ERROR: Expected false, got 0
2026-02-02 14:18:40,254 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_selected_channel_fail is equal to false
2026-02-02 14:18:40,254 INFO OK: read value = false
2026-02-02 14:18:40,254 INFO Check that B8_MsgBitReport degradation_conditions_w1_DegradationConditionsW1_total_rdr_fail is equal to false
2026-02-02 14:18:40,254 INFO OK: read value = false
2026-02-02 14:18:40,254 WARNING B8_Degradation: 1/12 failures
2026-02-02 14:18:40,254 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru1_gimbal is equal to false
2026-02-02 14:18:40,254 INFO OK: read value = false
2026-02-02 14:18:40,254 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru2_waveguide is equal to false
2026-02-02 14:18:40,254 INFO OK: read value = false
2026-02-02 14:18:40,254 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru3_waveguide is equal to false
2026-02-02 14:18:40,255 INFO OK: read value = false
2026-02-02 14:18:40,255 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru4_delta_guard_lna_switch is equal to false
2026-02-02 14:18:40,255 INFO OK: read value = false
2026-02-02 14:18:40,255 INFO Check that B8_MsgBitReport failure_location_pedestal_FailureLocationPedestal_sru5_waveguide_switch is equal to false
2026-02-02 14:18:40,255 INFO OK: read value = false
2026-02-02 14:18:40,255 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru10_main_computer is equal to false
2026-02-02 14:18:40,255 INFO OK: read value = false
2026-02-02 14:18:40,256 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru11_graphic_computer is equal to false
2026-02-02 14:18:40,256 INFO OK: read value = false
2026-02-02 14:18:40,256 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru12_power_supply is equal to false
2026-02-02 14:18:40,257 INFO OK: read value = false
2026-02-02 14:18:40,257 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru13_det_exp is equal to false
2026-02-02 14:18:40,257 INFO OK: read value = false
2026-02-02 14:18:40,257 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru14_rx_module is equal to false
2026-02-02 14:18:40,257 INFO OK: read value = false
2026-02-02 14:18:40,258 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru1_motherboard_chassis is equal to false
2026-02-02 14:18:40,258 INFO OK: read value = false
2026-02-02 14:18:40,258 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru2_mti_fft is equal to false
2026-02-02 14:18:40,258 INFO OK: read value = false
2026-02-02 14:18:40,258 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru3_dsp0 is equal to false
2026-02-02 14:18:40,258 INFO OK: read value = false
2026-02-02 14:18:40,258 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru4_dsp1 is equal to false
2026-02-02 14:18:40,258 INFO OK: read value = false
2026-02-02 14:18:40,258 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru5_cfar_px_ctrl is equal to false
2026-02-02 14:18:40,259 INFO OK: read value = false
2026-02-02 14:18:40,259 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru6_timer is equal to false
2026-02-02 14:18:40,259 INFO OK: read value = false
2026-02-02 14:18:40,259 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru7_post_processor is equal to false
2026-02-02 14:18:40,259 INFO OK: read value = false
2026-02-02 14:18:40,259 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru8_agc is equal to false
2026-02-02 14:18:40,259 INFO OK: read value = false
2026-02-02 14:18:40,260 INFO Check that B8_MsgBitReport failure_location_processor_FailureLocationProcessor_sru9_esa_if is equal to false
2026-02-02 14:18:40,260 INFO OK: read value = false
2026-02-02 14:18:40,260 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru1_chassis is equal to false
2026-02-02 14:18:40,260 INFO OK: read value = false
2026-02-02 14:18:40,260 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru2_uhf_assy is equal to false
2026-02-02 14:18:40,260 INFO OK: read value = false
2026-02-02 14:18:40,260 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru3_synthesizer is equal to false
2026-02-02 14:18:40,261 INFO OK: read value = false
2026-02-02 14:18:40,261 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru4_delta_guard_down_converter is equal to false
2026-02-02 14:18:40,261 INFO OK: read value = false
2026-02-02 14:18:40,261 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru5_sum_down_converter is equal to false
2026-02-02 14:18:40,261 INFO OK: read value = false
2026-02-02 14:18:40,261 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru6_lo_distributor is equal to false
2026-02-02 14:18:40,261 INFO OK: read value = false
2026-02-02 14:18:40,263 INFO Check that B8_MsgBitReport failure_location_receiver_FailureLocationReceiver_sru7_up_converter is equal to false
2026-02-02 14:18:40,263 INFO OK: read value = false
2026-02-02 14:18:40,263 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru1_chassis is equal to false
2026-02-02 14:18:40,263 INFO OK: read value = false
2026-02-02 14:18:40,263 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru2_delta_guard_lna is equal to false
2026-02-02 14:18:40,263 INFO OK: read value = false
2026-02-02 14:18:40,264 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru3_sum_act_prot_lna is equal to false
2026-02-02 14:18:40,264 INFO OK: read value = false
2026-02-02 14:18:40,264 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru4_4port_circulator is equal to false
2026-02-02 14:18:40,264 INFO OK: read value = false
2026-02-02 14:18:40,264 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_delta_guard is equal to false
2026-02-02 14:18:40,264 INFO OK: read value = false
2026-02-02 14:18:40,264 INFO Check that B8_MsgBitReport failure_location_rx_frontend_FailureLocationRxFrontEnd_sru5_stc_sum is equal to false
2026-02-02 14:18:40,265 INFO OK: read value = false
2026-02-02 14:18:40,265 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru1_chassis is equal to false
2026-02-02 14:18:40,265 INFO OK: read value = false
2026-02-02 14:18:40,265 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru2_power_supply is equal to false
2026-02-02 14:18:40,265 INFO OK: read value = false
2026-02-02 14:18:40,266 INFO Check that B8_MsgBitReport failure_location_servoloop_FailureLocationServoloop_sru3_digital_controller is equal to false
2026-02-02 14:18:40,266 INFO OK: read value = false
2026-02-02 14:18:40,266 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru1_chassis is equal to false
2026-02-02 14:18:40,266 INFO OK: read value = false
2026-02-02 14:18:40,266 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru2_rex_f_tx is equal to false
2026-02-02 14:18:40,267 INFO OK: read value = false
2026-02-02 14:18:40,267 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru3_power_supply is equal to false
2026-02-02 14:18:40,267 INFO OK: read value = false
2026-02-02 14:18:40,267 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru4_valve_el_twt_tx is equal to false
2026-02-02 14:18:40,267 INFO OK: read value = false
2026-02-02 14:18:40,267 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru5_rf_driver is equal to false
2026-02-02 14:18:40,267 INFO OK: read value = false
2026-02-02 14:18:40,268 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru6_controller_tx is equal to false
2026-02-02 14:18:40,268 INFO OK: read value = false
2026-02-02 14:18:40,268 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru7_hv_power_supply is equal to false
2026-02-02 14:18:40,268 INFO OK: read value = false
2026-02-02 14:18:40,268 INFO Check that B8_MsgBitReport failure_location_transmitter_FailureLocationTransmitter_sru8_eht_power_supply is equal to false
2026-02-02 14:18:40,269 INFO OK: read value = false
2026-02-02 14:18:40,269 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc10_pulse_compressor_interface is equal to false
2026-02-02 14:18:40,269 INFO OK: read value = false
2026-02-02 14:18:40,269 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc11_dp_interface is equal to false
2026-02-02 14:18:40,269 INFO OK: read value = false
2026-02-02 14:18:40,270 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc13_taxi_running is equal to false
2026-02-02 14:18:40,270 INFO OK: read value = false
2026-02-02 14:18:40,270 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc14_external_xyp_ram is equal to false
2026-02-02 14:18:40,270 INFO OK: read value = false
2026-02-02 14:18:40,270 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc15_servoloop_interface is equal to false
2026-02-02 14:18:40,271 INFO OK: read value = false
2026-02-02 14:18:40,271 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc1_internal_xyp_ram is equal to false
2026-02-02 14:18:40,271 INFO OK: read value = false
2026-02-02 14:18:40,271 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc2_external_xyp_ram is equal to false
2026-02-02 14:18:40,271 INFO OK: read value = false
2026-02-02 14:18:40,271 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc5_dual_port_ram is equal to false
2026-02-02 14:18:40,271 INFO OK: read value = false
2026-02-02 14:18:40,271 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc6_agc_machine is equal to false
2026-02-02 14:18:40,272 INFO OK: read value = false
2026-02-02 14:18:40,272 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc7_sat_machine is equal to false
2026-02-02 14:18:40,272 INFO OK: read value = false
2026-02-02 14:18:40,273 INFO Check that B8_MsgBitReport agc_test_results_AGCTestResults_test_agc9_c_ram_xy_checksum is equal to false
2026-02-02 14:18:40,273 INFO OK: read value = false
2026-02-02 14:18:40,274 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp10_video_memory is equal to false
2026-02-02 14:18:40,274 INFO OK: read value = false
2026-02-02 14:18:40,274 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp11_video_unit is equal to false
2026-02-02 14:18:40,274 INFO OK: read value = false
2026-02-02 14:18:40,274 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp12_transputer_unit is equal to false
2026-02-02 14:18:40,274 INFO OK: read value = false
2026-02-02 14:18:40,274 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp13_scan_converter_polar_memory is equal to false
2026-02-02 14:18:40,274 INFO OK: read value = false
2026-02-02 14:18:40,274 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp14_scan_converter_format_converter is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp1_486_cpu_tests is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp2_486_interfaces_with_r3000_gc is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp3_486_interface_with_slc is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp4_slc_communications is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp5_r3000_cpu_tests is equal to false
2026-02-02 14:18:40,275 INFO OK: read value = false
2026-02-02 14:18:40,275 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp6_r3000_interfaces is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp7_1553_and_discretes is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp8_graphic_cpu is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport data_processor_test_results_DataProcessorTestResults_test_dp9_graphic_processors is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_array_status is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_delta_channel_fail is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,276 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_injection_fail is equal to false
2026-02-02 14:18:40,276 INFO OK: read value = false
2026-02-02 14:18:40,277 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_cal_noise_fail is equal to false
2026-02-02 14:18:40,277 INFO OK: read value = false
2026-02-02 14:18:40,277 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_pedestal_status is equal to false
2026-02-02 14:18:40,277 INFO OK: read value = false
2026-02-02 14:18:40,277 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_processor_status is equal to false
2026-02-02 14:18:40,278 INFO OK: read value = false
2026-02-02 14:18:40,278 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_receiver_status is equal to false
2026-02-02 14:18:40,278 INFO OK: read value = false
2026-02-02 14:18:40,278 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_rx_frontend_status is equal to false
2026-02-02 14:18:40,278 INFO OK: read value = false
2026-02-02 14:18:40,278 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_servoloop_status is equal to false
2026-02-02 14:18:40,278 INFO OK: read value = false
2026-02-02 14:18:40,279 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is1_upconverter_chain_levels is equal to false
2026-02-02 14:18:40,279 INFO OK: read value = false
2026-02-02 14:18:40,279 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is2_downconverter_chain_levels is equal to false
2026-02-02 14:18:40,279 INFO OK: read value = false
2026-02-02 14:18:40,279 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is3_antenna_status_inconsistent is equal to false
2026-02-02 14:18:40,279 INFO OK: read value = false
2026-02-02 14:18:40,279 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is4_tx_status_inconsistent is equal to false
2026-02-02 14:18:40,279 INFO OK: read value = false
2026-02-02 14:18:40,279 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_test_is5_tx_power_level is equal to false
2026-02-02 14:18:40,279 INFO OK: read value = false
2026-02-02 14:18:40,280 INFO Check that B8_MsgBitReport integrated_system_test_results_IntegratedSystemTestResults_transmitter_status is equal to false
2026-02-02 14:18:40,280 INFO OK: read value = false
2026-02-02 14:18:40,280 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp1_master_dsp is equal to false
2026-02-02 14:18:40,280 INFO OK: read value = false
2026-02-02 14:18:40,280 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp2_interface_card is equal to false
2026-02-02 14:18:40,280 INFO OK: read value = false
2026-02-02 14:18:40,280 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp3_cpu_cards is equal to false
2026-02-02 14:18:40,281 INFO OK: read value = false
2026-02-02 14:18:40,281 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp4_dma_bus is equal to false
2026-02-02 14:18:40,282 INFO OK: read value = false
2026-02-02 14:18:40,282 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp5_sp_interface is equal to false
2026-02-02 14:18:40,282 INFO OK: read value = false
2026-02-02 14:18:40,282 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp6_dp_interface is equal to false
2026-02-02 14:18:40,282 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp7_scan_converter_interface is equal to false
2026-02-02 14:18:40,284 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport post_processor_test_results_PostProcessorTestResults_test_pp8_agc_interface is equal to false
2026-02-02 14:18:40,284 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps1_power_supply is equal to false
2026-02-02 14:18:40,284 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport power_supply_test_results_PowerSupplyTestResults_test_ps2_over_temperature is equal to false
2026-02-02 14:18:40,284 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe1_lna is equal to false
2026-02-02 14:18:40,284 INFO OK: read value = false
2026-02-02 14:18:40,284 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_fe2_agc_attenuators is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx1_synthesizer_commands is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx2_synthesizer_internal_tests is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx3_uhf_oscillator_level is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx4_downconverter_lo_level is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport receiver_and_rx_frontend_test_results_ReceiverAndRxTestResults_test_rx5_upconverter_lo_level is equal to false
2026-02-02 14:18:40,285 INFO OK: read value = false
2026-02-02 14:18:40,285 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm16_calibration_sum_channel_fail is equal to false
2026-02-02 14:18:40,286 INFO OK: read value = false
2026-02-02 14:18:40,286 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm1_master_clock_level is equal to false
2026-02-02 14:18:40,286 INFO OK: read value = false
2026-02-02 14:18:40,286 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm2_expander_level is equal to false
2026-02-02 14:18:40,286 INFO OK: read value = false
2026-02-02 14:18:40,286 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm3_sum_channel_down_converter is equal to false
2026-02-02 14:18:40,287 INFO OK: read value = false
2026-02-02 14:18:40,287 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm4_dg_channel_down_converter is equal to false
2026-02-02 14:18:40,287 INFO OK: read value = false
2026-02-02 14:18:40,287 INFO Check that B8_MsgBitReport rx_module_test_results_RxModuleTestResults_test_rm5_noise_attenuators is equal to false
2026-02-02 14:18:40,288 INFO OK: read value = false
2026-02-02 14:18:40,288 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl10_agc_control is equal to false
2026-02-02 14:18:40,288 INFO OK: read value = false
2026-02-02 14:18:40,288 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl11_ad is equal to false
2026-02-02 14:18:40,288 INFO OK: read value = false
2026-02-02 14:18:40,288 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl12_das is equal to false
2026-02-02 14:18:40,288 INFO OK: read value = false
2026-02-02 14:18:40,289 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl13_serial_communications is equal to false
2026-02-02 14:18:40,289 INFO OK: read value = false
2026-02-02 14:18:40,289 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl14_taxi_interface is equal to false
2026-02-02 14:18:40,289 INFO OK: read value = false
2026-02-02 14:18:40,289 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl15_pedestal_centre_scan_location is equal to false
2026-02-02 14:18:40,289 INFO OK: read value = false
2026-02-02 14:18:40,289 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl1_low_voltage_power_supply is equal to false
2026-02-02 14:18:40,289 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl2_high_voltage_power_supply is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl3_motor_drivers is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl4_resolvers_power_supply is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl5_waveguide_switch is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl6_over_temperature is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,290 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl7_resolver_to_digital_conv is equal to false
2026-02-02 14:18:40,290 INFO OK: read value = false
2026-02-02 14:18:40,291 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl8_position_loop_error is equal to false
2026-02-02 14:18:40,292 INFO OK: read value = false
2026-02-02 14:18:40,292 INFO Check that B8_MsgBitReport servoloop_test_results_ServoloopTestResults_test_sl9_microprocessor is equal to false
2026-02-02 14:18:40,292 INFO OK: read value = false
2026-02-02 14:18:40,293 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp10_board_overall is equal to false
2026-02-02 14:18:40,293 INFO OK: read value = false
2026-02-02 14:18:40,293 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp11_attenuatori_antenna is equal to false
2026-02-02 14:18:40,293 INFO OK: read value = false
2026-02-02 14:18:40,293 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp14_external_sp_if is equal to false
2026-02-02 14:18:40,293 INFO OK: read value = false
2026-02-02 14:18:40,293 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp16_bcn is equal to false
2026-02-02 14:18:40,293 INFO OK: read value = false
2026-02-02 14:18:40,293 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp1_timer1_up is equal to false
2026-02-02 14:18:40,294 INFO OK: read value = false
2026-02-02 14:18:40,294 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp2_timer_dma_pxc_if is equal to false
2026-02-02 14:18:40,294 INFO OK: read value = false
2026-02-02 14:18:40,294 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp3_timer_internal is equal to false
2026-02-02 14:18:40,294 INFO OK: read value = false
2026-02-02 14:18:40,294 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp4_px_ctrl_comm is equal to false
2026-02-02 14:18:40,294 INFO OK: read value = false
2026-02-02 14:18:40,294 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp5_video1_without_ad is equal to false
2026-02-02 14:18:40,294 INFO OK: read value = false
2026-02-02 14:18:40,295 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp6_video1_with_ad is equal to false
2026-02-02 14:18:40,295 INFO OK: read value = false
2026-02-02 14:18:40,295 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp7_video2_ad_sync is equal to false
2026-02-02 14:18:40,296 INFO OK: read value = false
2026-02-02 14:18:40,296 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp8_video2_timer_sync is equal to false
2026-02-02 14:18:40,296 INFO OK: read value = false
2026-02-02 14:18:40,297 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9_ad_da is equal to false
2026-02-02 14:18:40,297 INFO OK: read value = false
2026-02-02 14:18:40,297 INFO Check that B8_MsgBitReport signal_processor_test_results_SignalProcessorTestResults_test_sp9b_wideband_expander is equal to false
2026-02-02 14:18:40,297 INFO OK: read value = false
2026-02-02 14:18:40,298 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx10_hv_ps_over_temperature_warning is equal to false
2026-02-02 14:18:40,298 INFO OK: read value = false
2026-02-02 14:18:40,298 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx11_twt_helix_over_current is equal to false
2026-02-02 14:18:40,299 INFO OK: read value = false
2026-02-02 14:18:40,299 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx12_cathode_to_helix_arc is equal to false
2026-02-02 14:18:40,299 INFO OK: read value = false
2026-02-02 14:18:40,299 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx13_twt_over_temperature_hazard is equal to false
2026-02-02 14:18:40,300 INFO OK: read value = false
2026-02-02 14:18:40,300 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx14_twt_over_temperature_warning is equal to false
2026-02-02 14:18:40,300 INFO OK: read value = false
2026-02-02 14:18:40,300 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx15_cathode_under_voltage is equal to false
2026-02-02 14:18:40,301 INFO OK: read value = false
2026-02-02 14:18:40,301 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx16_cathode_over_voltage is equal to false
2026-02-02 14:18:40,301 INFO OK: read value = false
2026-02-02 14:18:40,301 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx1_microprocessors is equal to false
2026-02-02 14:18:40,301 INFO OK: read value = false
2026-02-02 14:18:40,301 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx2_tx_rf_input is equal to false
2026-02-02 14:18:40,302 INFO OK: read value = false
2026-02-02 14:18:40,302 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx3_twt_rf_input is equal to false
2026-02-02 14:18:40,302 INFO OK: read value = false
2026-02-02 14:18:40,302 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx4_twt_rf_output is equal to false
2026-02-02 14:18:40,302 INFO OK: read value = false
2026-02-02 14:18:40,302 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx5_tx_rf_output_level is equal to false
2026-02-02 14:18:40,303 INFO OK: read value = false
2026-02-02 14:18:40,303 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx6_vswr is equal to false
2026-02-02 14:18:40,303 INFO OK: read value = false
2026-02-02 14:18:40,303 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx7_three_phase_input_power is equal to false
2026-02-02 14:18:40,303 INFO OK: read value = false
2026-02-02 14:18:40,303 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx8_low_voltage_power_supplies is equal to false
2026-02-02 14:18:40,303 INFO OK: read value = false
2026-02-02 14:18:40,304 INFO Check that B8_MsgBitReport transmitter_test_results_w1_TransmitterTestResultsW1_test_tx9_hv_ps_over_temperature_hazard is equal to false
2026-02-02 14:18:40,304 INFO OK: read value = false
2026-02-02 14:18:40,304 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx17_collector_under_voltage is equal to false
2026-02-02 14:18:40,304 INFO OK: read value = false
2026-02-02 14:18:40,305 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx18_collector_over_voltage is equal to false
2026-02-02 14:18:40,305 INFO OK: read value = false
2026-02-02 14:18:40,305 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx19_rectified_voltage is equal to false
2026-02-02 14:18:40,305 INFO OK: read value = false
2026-02-02 14:18:40,305 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx20_cathode_inv_current_fail is equal to false
2026-02-02 14:18:40,305 INFO OK: read value = false
2026-02-02 14:18:40,306 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx21_collector_inv_current_fail is equal to false
2026-02-02 14:18:40,306 INFO OK: read value = false
2026-02-02 14:18:40,306 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx22_waveguide_pressurization is equal to false
2026-02-02 14:18:40,306 INFO OK: read value = false
2026-02-02 14:18:40,306 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx23_grid_window_over_duty_alt is equal to false
2026-02-02 14:18:40,307 INFO OK: read value = false
2026-02-02 14:18:40,307 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx24_floating_deck_fail is equal to false
2026-02-02 14:18:40,307 INFO OK: read value = false
2026-02-02 14:18:40,307 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx25_floating_deck_ps_fail is equal to false
2026-02-02 14:18:40,307 INFO OK: read value = false
2026-02-02 14:18:40,307 INFO Check that B8_MsgBitReport transmitter_test_results_w2_TransmitterTestResultsW2_test_tx26_grid_window_over_duty is equal to false
2026-02-02 14:18:40,308 INFO OK: read value = false
2026-02-02 14:18:40,308 INFO [Run 2] B8 Diagnostics: 173 checked, 172 pass, 1 fail
2026-02-02 14:18:40,308 WARNING B8_Degradation: 1 failures - fail
2026-02-02 14:18:40,308 INFO 0.0s remaining ...
2026-02-02 14:18:40,309 INFO [Run 2] Serial: 3 total, 0 errors, 3 fatal, 3 recycles
2026-02-02 14:18:40,309 WARNING Session: GRIFO_M_PBIT : Repetition 2 of 2
Total Step 190: Success 186 (97.89%), Failed 4 (2.11%),
2026-02-02 14:18:40,309 INFO tgt_gen()
2026-02-02 14:18:40,321 INFO TgtMsg: 1 1
2026-02-02 14:18:40,321 INFO Tgt: 1 @ 1180
2026-02-02 14:18:40,321 INFO Check that B9 b9_t_num is between 1 and 2
2026-02-02 14:18:40,321 INFO OK: read value = 1
2026-02-02 14:18:40,322 INFO Check that B9 b9_t1_rng is between 1179 and 1186
2026-02-02 14:18:40,322 INFO OK: read value = 1180
2026-02-02 14:18:40,322 INFO Repetitions terminated.
2026-02-02 14:18:40,322 INFO [Report] Custom statistics data registered for PDF generation
2026-02-02 14:18:40,322 INFO ==========================================================================================
2026-02-02 14:18:40,322 INFO FINAL TEST STATISTICS SUMMARY
2026-02-02 14:18:40,323 INFO ==========================================================================================
2026-02-02 14:18:40,323 INFO Total Runs: 2
2026-02-02 14:18:40,323 INFO Successful: 1 (50.0%)
2026-02-02 14:18:40,323 INFO Failed: 1 (50.0%)
2026-02-02 14:18:40,323 INFO B6 Checks: 24 (Pass: 19, Fail: 2, Known: 3)
2026-02-02 14:18:40,323 INFO B8 Checks: 346 (Pass: 344, Fail: 2)
2026-02-02 14:18:40,323 INFO Serial: 3 messages (0 errors, 3 fatal, 3 recycles)
2026-02-02 14:18:40,324 INFO PBIT Timing: avg=0.23s, min=0.23s, max=0.24s, σ=0.00s
2026-02-02 14:18:40,324 INFO ==========================================================================================
2026-02-02 14:18:40,324 INFO Detailed statistics will be available in the PDF report
2026-02-02 14:18:40,324 INFO Exporting statistics to CSV: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_141840_statistics.csv
2026-02-02 14:18:40,331 INFO Statistics exported successfully to: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_141840_statistics.csv
2026-02-02 14:18:40,332 INFO Statistics exported successfully to JSON: C:\src\____GitProjects\SXXXXXXX_PyBusMonitor1553\__OLD\__TEST_GENOVA\GrifoAutomaticTestEnv\TestEnvironment\scripts\..\env\..\pdf_reports/GRIFO_M_PBIT\GRIFO_M_PBIT_20260202_141840_statistics.json
2026-02-02 14:18:40,334 INFO Set MAIN_POWER to False
2026-02-02 14:18:40,334 INFO [MOCK] Power OFF
2026-02-02 14:18:40,334 INFO [MOCK] 1553 Interface stopped
2026-02-02 14:18:45,337 INFO Check that MAIN_POWER is equal to 0
2026-02-02 14:18:45,337 INFO OK: read value = False
2026-02-02 14:18:45,337 INFO [MOCK] Serial terminal disconnected
2026-02-02 14:18:45,337 INFO Stop Time: 2026-02-02 14:18:07.837211
2026-02-02 14:18:45,337 INFO Test execution time: 0:00:37.499912